1 BEFORE USE
- 3 -
Environment
Operate the Programmable Controller in the following environment:
Table 1-1 Operating Environment
Supply voltage
100 to 120 VAC,
single-phase, 50/60 Hz
±
4%
Amplitude range
85 to 132 VAC
Temperature
At operation: 0 to 55
°
C; storage: -20 to 75
°
C
Relative humidity
At operation: 30 to 90% RH; storage: 10 to 90% RH
Vibration resistance
0.6 G (1000 rpm)
Shock resistance
10 G
Ambient air
Dust: 0.1 mg/m
3
or less (given that there is no corrosive gas)
Output
module
Furnish the output module load power supply with a fuse for the protection of load short-circuits.
Ensure that the employed fuse is rated to match the load. If the employed fuse rating is higher
than specified, the printed circuit boards, case, and other items may burnout when the load is
shorted.
Fuse
Load
Power
supply
S10mini
(output module)
Figure 1-2 Output Module Specifications