39
Service Parameters:
Para-
Descriptions
De-
Min. Max. Unit Res
meter fault
EV01
Water pump control
mode
Continuous
work
Continuous work or work by regulation
EV03
Water pump set temp.
difference on cooling
5 1
10
℃
0.1
EV04
Water pump set temp.
difference on heating
5 1
10
℃
0.1
SF01 Unit
type
Only heating or C Heating
SF05
Enable domestic hot
water function
YES
YES or NO
SF13
HW On/Off way
Keyboard
Keyboard or remote
SF14
AC On/Off way
Keyboard
Keyboard or remote
DF03
Defrost start outdoor
temperature
12 3.0
20.0
º
C
0.1
DF04
Defrost temperature
differential (OT-LPS))
13 5 20
º
C
0.1
DF05
Defrost start delay
after OT-LPS
≤
DF04
15 1 60
Sec
1
DF06
Minimum defrost
interval
30 15 60
Min 1
DF09
Defrost end HPS
temperature
35 1 40
º
C
0.1
DF10 Max.
defrost
time
360
1 1000 Sec
1
DF12
Defrost start
evaporation temp.
-2 -5 5 ºC
0.1
DF13
Fan start coil temp.
25
5
60
º
C
0.1
DF15
De icing heater start
ambient temperature
2 -10
10 ºC
0.1
UI01 Service
password
0000 9999 -
1
Service parameter is code protected and only could be adjusted when unit is OFF.
Service Parameters
Summary of Contents for AS10S/L
Page 3: ...2 Nomenclature ...
Page 9: ...8 Positioning 1 550mm 600mm 550mm 600mm Positioning ...
Page 35: ...34 Three curves of different ST05 setting User Guide ...
Page 60: ...59 Dimensions AS10S L AS13S L 1096 550 500 1040 143 476 151 AS20S L Dimensions ...
Page 63: ...62 AS20S L m3 h 10 20 30 1 0 2 0 3 0 4 0 40 KPa 5 0 Water Pressure Plots ...
Page 64: ...63 Temperature and sensor resistance table Temperature and sensor resistance table ...