12
Heating Mode Working Principle:
On heating mode
a. When SF04:enable compensation=NO,
When the Inlet water temperature
≤
RTc-ST04 (RTc is the actual Inlet water
temperature of the last stop) ,the compressor will start to heat. After outlet water temp.
B2
≥
ST02, compressor will stop. The Compressor will start again when Inlet water
temperature
≤
RTc-ST04,.
b. When SF04 enable compensation=YES,
ST02 is replaced by “Set temperature at heating” =ST05+ST06/10 *(ST05-OT).
Refer to chapter “Heating compensation curve setting” .