4 Setting Up
Version 04 05/2014
4.6 Setting compatibility, operating mode and transmitting powerpower
4.6 Setting compatibility, operating mode and transmitting power
Please note:
The OZD Profi 12M … PRO must be switched off when
changing the operating mode.
You can switch off the OZD Profi 12M … PRO by, e.g.,
unplugging the 7-pin terminal block.
4.6.1 Setting the compatibility
The DIL switch S7 is used to switch the functional
compatibility to devices of the preceding generation
OZD Profi P3a, … P4a, … G3a, … G4a,… G3a-1300 and
… G4a-1300 either off or on. Default setting at S7 is
Position 0 (compatibility is switched off).
DIL switch S7 (compatibility) in
Position 0:
compatibility
to
OZD Profi P3a, OZD Profi P4a,
OZD Profi G3a, OZD Profi G4a,
OZD Profi G3a-1300 and
OZD Profi G4a-1300
switched off
DIL switch S7 (compatibility) in
Position 1:
compatibility
to
OZD Profi P3a, OZD Profi P4a,
OZD Profi G3a, OZD Profi G4a,
OZD Profi G3a-1300 and
OZD Profi G4a-1300
switched on
0
1
S 6
S 7
S 1
S 2
S 4
S 5
S 3
S 0
0
1
S 6
S 7
S 1
S 2
S 4
S 5
S 3
S 0
The
functional compatibility
to OZD Profi repeaters
OZD Profi P3a, … P4a, … G3a, … G4a, … G3a-1300 and
… G4a-1300 is
switched on
with the
DIL switch S7=1
.
This operating mode is required when operating this
repeater together with new devices.
Only turn switch S7 to Position 1 if the OZD Profi 12M …
PRO is being used as a spare or expansion device in
existing networks in conjunction with OZD Profi P3a, …
P4a, … G3a, … G4a, … G3a-1300 and … G4a-1300 and
a direct optical connection is to be made.
The following table shows the switch assignment of the
OZD Profi OZD Profi 12M … PRO at S7=1 as a spare
device for OZD Profi P3a, … P4a, … G3a, … G4a, …
G3a-1300 and … G4a-1300.
S0
Reserved
S1
Mode
Monitor
0
Line/Ring
ON
1
Line
OFF
S2
Redundancy
0
OFF
1
ON
S3, S4
Reserved
S5
Output Power CH 2
0
Standard
1
High
S6
Output Power CH 3
0
Standard
1
High