With a non-redundant supply of the supply voltage, the device reports the
loss of a supply voltage. You can prevent this message by changing the
configuration in the Management.
Connect the electrical wires to the socket according to the pin
assignment.
Type and specification
of the supply voltage
Pin assignment
Rated voltage
24 V DC
1 Plus terminal of supply
voltage 1
Voltage range incl.
maximum tolerances
16.8 V DC ... 32 V DC
2 Signal contact
3 Minus terminal of supply
voltages 1 and 2
4 Plus terminal of supply
voltage 2