![Hirschmann Octopus II User Manual Download Page 36](http://html1.mh-extra.com/html/hirschmann/octopus-ii/octopus-ii_user-manual_2138111036.webp)
36
Installation Octopus II
Release 06 10/2018
2.3
Connecting the ferrite
Note:
Exclusively for device variants with characteristic value hardware
type 0 (Standard) in connection with supply voltage characteristic values M9,
N9 or for device variants with the supply voltage characteristic value PP:
To adhere to EMC conformity, you connect the ferrite supplied to the voltage
input via the power supply cable.
Note:
To open the ferrite use the key supplied.
Insert the power supply cable through the ferrite 1 time.
Position the ferrite as close as possible to the voltage input (max. distance
19.7 in (50 cm)).
Lock the ferrite.
2.4
Connecting the power supply and the signal
contact lines
2.4.1
Supply voltage with the characteristic value BB
A 5-pin M12 plug is available for the redundant supply to the device.
You find the prescribed tightening torque in chapter:
See “Technical data” on page 49.
The supply voltage is connected to the device casing through protective
elements exclusively.
You have the option of supplying the supply voltage redundantly, without
load distribution.
WARNING
ELECTRIC SHOCK
Before connecting the electrical wires,
always
verify that the requirements
listed are complied with.
See “Requirements for connecting electrical wires” on page 6.
Failure to follow this instruction can result in death, serious injury, or
equipment damage.