Commissioning
4.4 Preconfiguration of the output signals (current/voltage)
The analog signal outputs (channels 1 to 4) are commonly preconfigured in the factory as 4-20 mA
current outputs. If necessary the signal outputs can also be commonly configured as voltage out-
puts.
NOTE
The signal outputs (channels 1 to 4) can be commonly configured either as current outputs
or as voltage outputs. A mixed configuration is not possible!
The conversion is made by changing the
jumpers
on the circuit board and subsequently selecting
the signal range via the
programming button
. These elements are only accessible after opening
the device. (See chapter 4.3)
How can the outputs
be configured as
voltage outputs?
The jumpers for configuring the output signals are located above the LEDs for the corresponding
channels 1 - 4:
Jumper
Now set the jumpers
identically for each channel
according to the sketch below:
▲
Jumper setting
for
current
outputs
(standard)
▲
Jumper setting
for
voltage
outputs
NOTE
If you have configured the signal outputs as voltage outputs, it is also necessary to select
the signal range. (See chapter 5.4)