Internal
5.3、
Switch setting
:
No
Option
Definition
Default
Adjustment Range
3.1
Signal hold time
Pulse time of the opening and
closing relay output
0.5S
0.1-20.0S
3.2
Action timeout time
When the output pulse is timed,
If DI is not detected within the
set time, the alarm is given
0.5S
0.1-90.0S
3.3
Interlock time
The waiting time of the interlock
that before or after the closing of
the TIE Breaker
0.5
0-2.0S
5.4、
Programmable Control
:
Input function
No
Option
Default
Adjustment Range
4.1
Digital Input
1-2
4.1.x.1
Input function
4.1.x.2
Contact Type
NO
NO/NC
4.1.x.3
Input delay
0.05S
0.01-600.00S
4.2
Digital Output
0
4.2.x.1
Output function
4.2.x.2
Contact Type
NO
NO/NC
Input Menu
Input code definition
Inhibit
Inhibit input function
Forced to pos.
0
The transfer switch is immediately driven to 0 position,and the controller in manu mode,
meantime,when the input signal disappear,the controller feedback to auto mode
Priority
Priority network select; change S1 or S2 priority state when input is activated, return to
current priority state when input is not activated
Remote
control
Remote control is enable when input is activated
Remote
position I
Switch transfer to position I when input is activated
Remote
position II
Switch transfer to position II when input is activated
Remote
position 0
Switch transfer to position 0 when input is activated
Test off load
Activates on an off load test,this will start/stop the generator without transferring the load
to S2
Test on load
Activates on an on load test,this will start/stop the generator with transferring the load to
S2
LS
Verify the generator don’t overload before transfer to S2