notes
:
INPUT1, INPUT2 and INPUT3 solidify for detecting Qs1, Qs2 and Qtie open or close state
;
INPUT4,
INPUT5 and INPU6 solidify for detecting the fault state of Qs1, Qs2 and Qtie.
Output function
Output Menu
Output code definition
Inhibit
Inhibit output function
ATS ready
The output signal is activated when switch and controller are OK
SI available
The output signal is activated when SI available
SII available
The output signal is activated when SII available
Alarm
The output signal is activated when controller failure
Manu mode
The output signal is activated when controller in manu mode
Auto mode
The output signal is activated when controller in auto mode
Test mode
The output signal is activated when controller in auto mode
Position I
The output signal is activated when ATS in position I
Position II
The output signal is activated when ATS in position II
Position 0
The output signal is activated when ATS in position 0
Forced to pos. 0
The output signal is activated when ATS forced to 0 position
LS
Verify the generator don’t overload before transfer to S2
ATS Source N
Auxiliary Source N
ATS Source A
Auxiliary Source A
ATS Source B
Auxiliary Source B
ATS Source C
Auxiliary Source C
Start generator
When APP is M-G/G-M, the mains source failure
,
the output signal is activated
Universal
The Communication control
5.5、
Communication parameters
No
Option
Default
Adjustment Range
6.1
Serial node address
3
001-254
6.2
Serial Baud rate
19200
2400/4800/9600/
19200/38400
6.3
Data format
8N
8N/8O/8E/7O/7E
6.4
Stop bit
1
1/2
5.6、Language :
No
Option
Definition
Default
6.1
Language setting
\
Chinese
Chinese/English