Internal
2
.
Front panel touch button function
Icon
Key name
Function description
101
Key
In Manual mode, press this button to transfer breakers S1-
TIE-S2 to ON-OFF-ON(101 )
110
Key
In Manual mode, press this button to transfer breakers S1-
TIE-S2 to ON-ON-OFF (110 )
011
Key
In Manual mode, press this button to transfer breakers S1-
TIE-S2 to OFF-ON-ON (011 )
100
Key
In Manual mode, press this button to transfer breakers S1-
TIE-S2 to ON-OFF-OFF (100 )
001
Key
In Manual mode, press this button to transfer breakers S1-
TIE-S2 to OFF-OFF-ON (001 )
000
Key
In Manual mode, press this button to transfer breakers S1-
TIE-S2 to all OFF (000 )
Test mode
Key
Press this Key for 3 seconds to enter test function
Auto mode Key
Press this Key for 3 seconds to set controller as Auto
mode.
Manual mode
Key
Press this Key for 3 seconds to set controller as manual
mode
Programming
mode Key
Press this Key for 3 seconds to set controller as
programming mode.
Increase/ up Key
In menu page, press this Key to scroll page.
In parameter setting page.
Press this key to up cursor or increase value.
Decrease / down
Key
In menu page, press this Key to scroll page.
In parameter setting page.
Press this key to down cursor or decrease value..
Enter Key
Press this Key to enter sub-menu or confirm setting
information.
Return Key
Press this Key to return prior menu screen, press this button
for 3 seconds to lock/unlock the button. press it can clear
fault alarm when alarm occur.