Internal
4
.
Working mode
●
Programming mode: Parameter setting operation under this mode, long pressing “programming mode”
key for 3s to enter, set password before visiting programming menu
.
●
Manual mode: Can control switch manually, long pressing “manual mode” button for 3s to enter,
pressing 101 key
、
110 key
、
011 key
、
100 key
、
001 key
、
000 key switch the switch to the corresponding
state.
●
Automatic mode: Long pressing “automatic mode” button for 3s to enter. Under automatic mode, device
automatically executes operation of open/close switch and start/stop generator. When the time of
exceeding limit of prior source is longer than the set delay time, the device will open the load of the main
source and connect to the emergency source.
5
.
Main menu
●
Main menu consists of Public parameters, System parameters, Switch setting, Programmable Control,
communication parameters and Language Menu, Disconnect the alarm to make it convenient for user to
fast visit measuring value and revise parameters.
●
Parameter setting: This operation is only valid under the programming mode. When there are changes
of parameter, it will show “save parameter?” before returning to main menu. Select ”YES” to save
parameters
.