3 Product Description
X-CPU 01
Page 20 of 52
HI 801 009 E Rev. 4.00
3.4.15 Maintenance
Indicators
The maintenance LEDs are labeled
Maint
.
LED
Color
Status
Description
On
Forcing prepared, processor module in STOP, RUN
or RUN / UP STOP
Blinking1
Forcing active, processor module in RUN or
OPERATE
Force
Yellow
Off Forcing
inactive
On
Connection to the PADT with write permission
Blinking1
At least one user program is in the RUN_FREEZE
state (single step operation)
Test
Yellow
Off
No connection to the PADT with write access and
no user program in the RUN_FREEZE state
On
Download (processor module in STOP), the
configuration is being loaded,
A PADT write command is being processed
Blinking1
Reload procedure active or exchange of
configuration data between processor modules
Prog
Yellow
Off
No loading procedure active and no configuration
data exchange between processor modules
Table 9: Maintenance Indicators
3.4.16 Fault
Indicators
The fault LEDs are labeled
Fault
.
LED
Color
Status
Description
On
System warning, only if no module fault occurred in a
HIMax system module.
Blinking1
Faults detected in a HIMax system module, e.g.,
hardware, software, over temperature or power supply.
The module or base plate is missing or does not match
the configuration or cannot be operated as intended.
System
Red
Off
No module fault displayed for a HIMax system module
On
Field warning, only if no field fault occurred in a HIMax
system I/O module
Blinking1
Field faults in an I/O module of the HIMax system
Field
Red
Off
No field faults displayed for an I/O module in the
HIMax system
On
COM warning, only if no faults occurred in the external
process data communication
Blinking1
Fault in the external process data communication
Com
Red
Off
No faults displayed for the external process data
communication
Table 10: Fault Indicators