X-CPU 01
3 Product Description
HI 801 009 E Rev. 4.00
Page 25 of 52
3.5 Product
Data
Parameter
Value
Supply voltage
24 VDC, -15 %...+20 %, r
P
≤
5 %, SELV,
PELV
Current input
1.4 A
Fuse (internal)
7.5 A
Microprocessor PowerPC
Flash EPROM
128 MB
DDRAM, NVRAM
256 MB
Program memory for each user program
1023 kB
Data memory for variables per user program
1023 kB
Total program and data memory for all user
programs
10 MB less 4 kBytes for CRCs
Data memory for retain variables
per user program
2 kB
A total for all user programs
32 kB
Number of variables being able to trigger
events
20 000
Number of events that can be stored
5000
Safety time
≥
20 ms, depending on the application
Buffer for date/time
Gold capacitor
Operating temperature
0 °C...+60 °C
Storage temperature
-40 °C...+85 °C
Humidity
max. 95 % relative humidity, non-
condensing
Type of protection
IP20
Dimensions (H x W x D) in mm
approx. 310 x 29.2 x 236
Weight
approx. 1.3 kg
Table 15: Product Data