F3 DIO 16/8 01
4 Start-up
HI 800 177 E Rev. 2.00
Page 37 of 60
4.3.3
Digital Outputs of F3 DIO 16/8 01
The following table presents the statuses and parameters for the output module (DO 8 03) in the
same order given in the SILworX Hardware Editor.
4.3.3.1
Tab:
Module
The
Module
tab contains the following system parameters:
System parameter
Data
type
R/W
Description
DO.Error Code
WORD
R
Error codes for all digital outputs
Coding
Description
0x0001
Fault within the digital outputs
0x0002
Test of safety shutdown returns a fault
0x0004
Test of auxiliary voltage returns a fault
0x0008
FTT test of test pattern faulty
0x0010
Output switch test pattern faulty
0x0020
Output switch test pattern (shutdown test of the
outputs) faulty
0x0040
Active shutdown via WD faulty
0x0080
FTT test of monitoring time returns a fault
0x0100
FTT read back of monitoring time returns a fault
0x0200
All outputs are switched off, total current
exceeded
0x0400
FTT test: 1st temperature threshold exceeded
0x0800
FTT test: 2nd temperature threshold exceeded
0x1000
FTT test: Monitoring of auxiliary voltage 1:
Undervoltage
0x2000
FTT test: Monitoring of auxiliary voltage 2:
Undervoltage
0x4000
Flipflop of the voltage monitoring (18 V)
provides undervoltage
0x8000
Test of monitoring time returns a fault
DO.Line Monitoring
Time
UINT
W
Monitoring time for line diagnosis in [ms],
Range 1...50 ms, Default: 0 ms
DO.LM period
WORD
W
Period [s] required for the line diagnosis
Range 1…100 s, 1 s steps
DO[xx].SC
Monitoring with
Reduced Voltage
BOOL
W
Line diagnosis with reduced voltage
Coding
Description
FALSE
Normal signal voltage level
TRUE
Reduced signal voltage level
(Reduced signal voltage level with
Line Monitoring [BOOL] ->
=
TRUE only)