F3 DIO 16/8 01
4 Start-up
HI 800 177 E Rev. 2.00
Page 35 of 60
4.3.2.1
Tab:
Module
The
Module
tab contains the following system parameters:
System parameter
Data
type
R/W Description
DI Number of
Pulsed Channels
USINT
W
Number of pulsed outputs (supply outputs)
Coding
Description
0
No pulsed output planned for SC/OC
1)
detection
1
Pulsed output 1 planned for SC/OC
1)
detection
2
Pulsed output 1 and 2 planned for SC/OC
1)
detection
Pulsed outputs must not be used as safety-related outputs!
DI Supply [01]
BOOL
W
DI Supply [02]
BOOL
W
Triggering the single DI supplies
Coding
Description
FALSE
Sensor supply (1 A) is off.
TRUE
Sensor supply (1 A) is on.
Default setting FALSE: Feeding current 40 mA
DI Pulse Slot
UDINT
W
Pulse module slot
(SC/OC
1)
detection), set the value to 3
DI Pulse Delay [µs]
UINT
W
Waiting time for line control (detection of short-circuits or cross-
circuits)
DI.Error Code
WORD
R
Error codes for all digital inputs
Coding
Description
0x0001
Fault within the digital inputs
0x0002
FTT test of test pattern faulty
DI.Error Code
Supply
WORD
R
Error code of the DI supply unit as a whole
Coding
Description
0x0001 Module
fault
DI[01].Error Code
Supply
BYTE R
DI[02].Error Code
Supply
BYTE R
Error codes of the single DI supplies
Coding
Description
0x01
Error DI supply unit
0x02
Supply shutdown due to overcurrent
0x04
Error while reading back the supply
Module Error Code
WORD
R
Module error code
Coding
Description
0x0000
I/O processing, if required with errors
see other error codes
0x0001
No I/O processing (remote I/O not in RUN)
0x0002
No I/O processing during the booting test
0x0004
Manufacturer interface operating
0x0010
No I/O processing: invalid configuration
0x0020
No I/O processing: fault rate exceeded
0x0040/
0x0080
No I/O processing: configured module not
plugged in
Module SRS
UDINT
R
Slot number (System Rack Slot)
Module Type
UINT
R
Type of module, target value: 0x00E2 [226
dec
]
1)
SC/OC
(short-circuits/open-circuits)
Table 24: SILworX - System Parameters for Digital Inputs,
Module
Tab