![hilscher netTAP NT 50 Series User Manual Download Page 80](http://html1.mh-extra.com/html/hilscher/nettap-nt-50-series/nettap-nt-50-series_user-manual_2134827080.webp)
Wiring Instructions
80/86
netTAP NT 50 | Gateway Devices
DOC091202UM09EN | Revision 9 | English | 2013-02 | Released | Public
© Hilscher, 2010-2013
Cable Requirements:
The workmanship of bus cabling is an important factor of the reliable opera-
tion and also for the electromagnetic compatibility and emission. It is man-
datory to use shielded twisted-pair cables. The shield of the cable must
consist of a copper wire mesh.
Parameter
Value
Characteristic wave
impedance
150
Ω
± 15
Ω
Capacitance
< 30 pF/m
Loop resistance
110
Ω
/km
Wire gauge
0,64 mm
Table 78: Electric Requirements to RS-422 Cables
The following lengths of lines can be achieved:
Max. overall length of
line
Max. Baud rate
Max. length of a single
branch line
120 m
1 MBit/s
0,3 m
600 m
500 kBit/s
0,6 m
1200 m
100 kBit/s
1,5 m
Table 79: RS-422 Conductor Length and Transmission Rates