LEDs
55/64
COM-C | Communication Module
DOC021001DG12EN | Revision 12 | English | 2011-06 | Released | Public
© Hilscher, 2002-2011
4.1.10
PROFIBUS DP Master
LED
Color
State
Meaning
yellow
Flashing cyclic at 1Hz
Device is in boot loader mode and is waiting for firmware download
yellow
Flashing cyclic at 5Hz
Firmware download is in progress
yellow
Flashing irregular (*)
Hardware or heavy runtime error detected
green
On
Communication is running, the device has established at least one
configured fieldbus connection
green
Flashing cyclic at 5Hz
No error in the configuration found, communication is stopped or ready
for communication but no connection to any slave
green
Flashing irregular (*)
Power Up: Configuration missing or faulty, device needs commission-
ing, Runtime: Host Watchdog timeout
SYS
-
Off
Device has no power supply or hardware defect
yellow
On
Devise is holding the PROFIBUS Token and is able to transmit tele-
grams
yellow
Flashing irregular (**)
Devise is sharing the PROFIBUS Token with other Master devices in
the PROFIBUS network
red
On
Device has found a communication problem to at least one PROFIBUS
DP Slave or has detected a short circuit
COM
-
Off
Device is not configured or has not received the Token permission on
the PROFIBUS network
Table 35: LED PROFIBUS DP Master (COM)
(*) 3 times fast at 5 Hz, 8 times between 0,5 Hz und 1 Hz
(**) between 0,5 Hz and 1 Hz
4.1.11
PROFIBUS DP Slave
LED
Color
State
Meaning
yellow
Flashing cyclic at 1Hz
Device is in boot loader mode and is waiting for firmware download
yellow
Flashing cyclic at 5Hz
Firmware download is in progress
yellow
Flashing irregular (*)
Hardware or heavy runtime error detected
green
On
Slave in cyclic data exchange with DP Master
green
Flashing cyclic at 5Hz
Slave has no cyclic data exchange with DP Master
green
Flashing irregular (*)
Power Up: Configuration missing or faulty, device needs commission-
ing, Runtime: Host Watchdog timeout
SYS
-
Off
Device has no power supply or hardware defect
yellow
On
Slave has received parameter data / configuration data from DP Mas-
ter and has reached the state data exchange
red
On
Application program (communication mode: bus synchronous / device
controlled) not longer synchronous to bus cycle
COM
-
Off
Slave has not reached the state data exchange
Table 36: LED PROFIBUS DP Slave (COM)
(*) 3 times fast at 5 Hz, 8 times between 0,5 Hz und 1 Hz