October 13, 2003
is444re
Page 7 of 24
DRAFT 08/27/03
Determining the Wall/Construction Type
WARNING:
The installation method differs for each wall and construction type. Failure to
determine the wall and construction type could result in personal injury or
equipment damage.
1.
Before proceeding, refer to the local or state building codes, and determine the type of
wall (D) and construction type (see figure 2 on page 4):
•
Seismic walls are constructed to prevent damage from an earthquake.
•
Non-seismic walls are not constructed to prevent damage from an earthquake.
•
Fire-rated walls are constructed to prevent the spread of fire.
•
Non-fire-rated walls are not constructed to prevent the spread of fire.
2.
Perform one of the following:
•
On seismic walls, install the wall backing plates according to the Office of
Statewide Health, Planning, and Development (OSHPD)-approved drawings
and the as-built drawings, and then go to “Installing the Medical Gas Drops”
on page 7.
NOTE:
For seismic construction requirements, contact Hill-Rom Technical Support at
800-445-3720.
•
On non-seismic walls (both fire and non-fire-rated), go to “Installing the Med-
ical Gas Drops” on page 7.
Installing the Medical Gas Drops
1.
To locate the connections to the medical gas supplies, refer to the as-built drawings for
the Integris® 2001B Headwall System.
2.
Ensure that the connections to the medical gas supply are located in the center of the
vertical chase (B) or (C), with the oxygen supply connection oriented closest to the
raceway (A) (see figure 4 on page 8). If the connections are not properly located, a
contractor must relocate them.
3.
Install the medical gas service drops.
Summary of Contents for Itegris 2001B
Page 2: ......
Page 6: ...Table of Contents Page iv is444re October 13 2003 DRAFT 08 27 03 NOTES...
Page 10: ...Page 4 of 24 is444re October 13 2003 DRAFT 08 27 03 Figure 2 Component Identification...
Page 12: ...Page 6 of 24 is444re October 13 2003 DRAFT 08 27 03 Figure 3 Fasteners...
Page 14: ...Page 8 of 24 is444re October 13 2003 DRAFT 08 27 03 Figure 4 Medical Gas Drops Finished floor...
Page 24: ...Page 18 of 24 is444re October 13 2003 DRAFT 08 27 03 Figure 9 Hanger Bracket Installation...