Page: 35
6.6.2
EURO-ZEM8+PSU Input Configuration
Input Resistance
1k / 1k DEOL Range
4k7 / 2k2 DEOL Range
4k7 / 4k7 DEOL Range
Normal (closed state)
0k5 to 1k4
1k4 to 2k9
3k7 to 8k3
Burglary Alarm
1k5 to 5k9
4k2 to 7k8
8k4 to 10k2
Fault
6k to 8k1
8k to 11k3
10k3 to 14k9
Masking
8k2 to 17k
11k6 to 22k
15k to 22k
Tamper
<0k5 or >17K
<1k4 or >22k
<3k7 or >23k
All inputs are programmed in "CHANGE INPUTS" in the Engineer menu.
6.6.3
Addressing the EURO-ZEM8+PSU
NOTE
: The addressing is done by headers that represent the address. For example:
If a header is placed on
00
, and
0
, the address is
0
.
If a header is placed on
00
, and
9
, the address is
9
.
If a header is placed on
20
, and
3
, the address is
23
etc.
6.6.4
Adding the EURO-ZEM8+PSU (From the Engineer Menu)
Enter the engineer menu and scroll to 'INSTALL ZEM' and press
. Please see the Programming Manual for
more information.