MaxiProx DFM Reader Installation Manual 5375-901 Rev D
Page
8 of 20
2.8
2.8 DipSwitch and Jumper Settings
DipSwitch and Jumper Settings
Verify the default settings according to the model ordered, or set the DIPswitches and Jumper
positions according to the following.
Table 3: DIPSwitch and Jumper Settings
Switch
Default
Description
1. Interface mode 1
On
See mode chart table 6 below
2. Interface mode 2
On
See mode chart table 6 below
3. Interface mode 3
On
See mode chart table 6 below
4. Beeper control On/Off
On
On - beep after valid card read. Off - no beep after valid card read.
5. Green LED flash
O f f
O f f - flash after valid card read. On - no flash after v alid card read.
6. Single/Dual external LED
O f f
O f f - single line LED control. On - dual line LED control.
7. Serial Baud 1 control
O f f
See baud rate chart below.
8. Serial Baud 2 control
O f f
See Baud rate chart below.
Table 4: Interface Jumpers Description - P3 and P4
P3 and P4
1-2
See mode chart table 6 below
Table 5: Switch Description - SW2
Switch
Default
Description
1. Serial Baud 3 control
On
See baud rate table 7 below
2. Note address 0
N/A
Unused
3. Note address 1
N/A
Unused
4. Note address 2
N/A
Unused
5. Note address 3
N/A
Unused
6. Note address 4
N/A
Unused
7. Unused
8. Unused
Table 6: Mode Chart
Mode
SW1-1
SW1-2
SW1-3
SW5-3
SW5-4
SW5-5
P3 & P4
Jumpe rs
Wiegand
ON
ON
ON
NA
NA
NA
1-2
Clock & Data
OFF
ON
ON
NA
NA
NA
1-2
RS232
ON
OFF
ON
NA
OFF
OFF
2-3
RS422
terminated
OFF
OFF
ON
ON
OFF
OFF
2-3
RS422
unterm.
OFF
OFF
ON
OFF
OFF
OFF
2-3
Table 7: Baud Rate Chart – RS232 and RS422
BAUD
SW1-7
SW1-8
SW2-1
9600
ON
ON
ON
4800
OFF
ON
ON
2400
ON
OFF
ON
1200
OFF
OFF
ON