FRU Replacement Guide
3 Controller Node Replaceable Units
16
c) In the
Commands
pane, click
Shutdown
.
Figure 2: The Shutdown Button in the Commands Pane
d) Wait for the
Status
field to change to
DONE
.
4.
Go to the rack and identify the correct chassis by the blinking blue LED on its front and back panels.
5.
Remove the failed chassis from the rack.
a) At the front of the chassis, loosen the rack mounting screws.
b) At the back of the chassis, disconnect the five network cables connected to the ports labeled as follows in the
image below.
Important:
Pull very gently on the pull tabs of the SFP+ cables, otherwise they might break.
Note:
Check that the cables are labeled correctly, so that you can put them back in the same
order.
a. N1
(remove the SFP+ optical transceiver attached to the cable)
b. N2
c. N3
d. N4
(remove the SFP+ optical transceiver attached to the cable)