Operation
Emergency Stop
Pressing the emergency stop
pushbutton will immediately stop
the engine and prevent it from
restarting.
The emergency stop button must
only be used to stop the machine
in an emergency and not to stop the set during normal
operation.
To restart the generator, release the emergency stop
button by twisting clockwise, reset the control module
by pressing the Fault Reset button, and start the
generator by pressing the green Run button.
Terminal Output Pod
WARNING
Risk of Electrocution. Disconnect Power before
making electrical connections.
Terminal connections should be made by quali
fi
ed
personnel only.
NOTICE
The generator will not start if the Terminal Pod
Cover is Open.
The Terminal Output Pod can be accessed by
removing the Terminal Output cover’s wingnuts. The
cover is hinged from the bottom and folds down to
reveal the terminals.
(1)
(2)
(3)
(4)
(5)
Item
Description
1
Three Phase and Neutral Terminal
Connections
2
Remote Connection Terminals
3
Auto Shutdown Switch
4
Cable Gland
5
Earth Stud
If the set has been con
fi
gure to provide terminal
output supply and or remote control, the electrical
connections from the generator will have been made
and tested during installation. All cables connecting
to external panels and output will have been passed
through the cable gland opening.
Three Phase Terminal Connections
Ensure that the connections are secure and correctly
sequenced. Please refer to the wirring diagram later in
this manual.
Remote Connection Terminals
These are to be used to connect the set to a remote
Automatic Mains Failure (AMF) panel, remote
control panel or timer volt free switch. The switched
connection can then transmit a start and stop signal
to the DSE4510 to initiate the generator start up or
shutdown procedure.
Please contact HGI sales to discuss any requirement
to extend the generator functionality for remote
connectivity.
Auto Shutdown Switch
There is a safety switch on the terminal output pod
door which prevents the generator from starting if
the door is open. This activates the emergency stop
circuit.
Earth Stud
The M10 brass stud in the terminal pod should be
connected to an external earth point or to an earth
spike. An earth spike can be supplied as an optional
extra and should be driven at least 600 mm into soil.