Technical data
Type
VORTEX 3000
Air flow rate max. (m³/h)
3,600
Compression (Pa)
550
Power connection (V/Hz)
230 V / 50 Hz
Electrical protection (A)
2.2
Power consumption max. (kW)
0.49
Protection class (motor/housing)
IP 44
Height x Width x Length (mm)
490 x 480 x 400
Weight (kg)
15
Sound level dB(A) 3m
83
Hose connection on both sides Ø mm
305
CAUTION:
Within the scope of further development, technical data may be changed without prior
announcement. Some values are approximate values.
8.
Fault finding and correction
WARNING
:
Maintenance work shall have to be carried out with the unit switched off, i.e. with mains plug removed.
PROBLEM
CAUSE
by
SOLUTION
Motor is not operating
No power.
The unit has not been switched
on.
Impeller is blocked
Air inlet or outlet is blocked.
Switch has broken off.
Loose wiring.
B
B
B
B
AST
AST
Connect the unit; check the fuse.
Switch the unit on.
Remove the reason for the blockage.
Switch the unit off and let it cool down; then
rRemove blockage.
Order replacement switch from the dealer or
HEYLO.
Check wiring and tighten, if required.
The motor is running, but
the impeller turns
irregularly or makes contact
A heavy impact has bent the
motor suspension so that the
impeller jams.
A heavy impact has caused the
motor to slip out of the
suspension so that the impeller
jams.
Safety broken due to excessive
load on the fan wheel.
AST
AST
AST
Remove the motor from the housing, replace or
repair the bent motor suspension.
Remove the motor from the housing, then place
the motor in the suspension correctly.
Safety splint must be replaced
Unit vibrates excessively
Collection of dirt on the wheel.
Unbalance of the impeller.
Impeller is bent.
Motor shaft is bent.
B
AST
AST
AST
Clean impeller.
Balance or replace the impeller.
Replace impeller.
Replace motor.
B = User AST = Authorised service technician
Ask your local dealer for spare parts or get in touch with HEYLO service department.