6/17

Description of the Relay Outputs

Please ensure that the outputs are volt-free.

AV desalination valve

Connect the desalination valve (solenoid or motor valve) to this relay output.

The idle position of the relay is the same in the case of a currentless controller and in the operating position: Contact to
terminals 10-11.

Set the time for desalination under menu option

"M"

 

º

 BASIC PROGRAM 

º

 PROGRAM VALUES 

º

 DESALINATION 

º

 Desalination time

.

DO   dosing output

Connect a dosing pump at this relay output (solenoid or motor dosing pump).

The idle position of the relay is the same in the case of a currentless controller and in the operating position: Contact to
terminals 13-14.

Set the time for the dosing impulse under menu option

"M"

 

º

 BASIC PROGRAM 

º

 PROGRAM VALUES 

º

 DOSING 

º

 Impulse Duration

.

Set the impulse ratio, for which quantity of water dosing should be carried out, under menu option

"M"

 

º

 BASIC PROGRAM 

º

 PROGRAM VALUES 

º

 DOSING 

º

 Litre/Impulse

.

Example:
A one second impulse should be provided per 50 litres: 
Litre/Impulse = 50.0, Impulse = 1.0sec

Alternatively, the output can emit a certain number of impulses with a settable impulse pause and duration for the
measured quantity of water.
Set the number of impulses under menu option

"M"

 

º

 BASIC PROGRAM 

º

 PROGRAM VALUES 

º

 DOSING 

º

 No. of Impulses

.

Example:
4 one second impulses with a 3 second pause should be provided per 50 litres.
Litre/Impulse = 50.0, Impulse duration = 1.0sec, Impulse pause = 3.0sec, No. of impulses = 4

Note!
The impulse ratio in litres/impulse should not be less than the basic number of the water meter.

EV input valve
This output is not available if you have programmed the “Draining” function !

Connect the input valve (solenoid or motor valve) for shutting off the supply to this relay output.

Set the time (time and weekday) and the duration for draining the system under the menu option

"M"

 

º

 BASIC PROGRAM 

º

 PROGRAM VALUES 

º

 OUTPUT AL/EV

.

AL error message output ("Alarm")
This output is not available, if you have programmed the “Draining“ function !

Output "AL" is a volt-free change-over relay contact. During trouble-free operation, the contact between terminals 16 - 18
is closed and the one between terminals 16 - 17 is open. During voltage loss or if an error occurs, the contact between
terminals 16 - 17 is closed and the one between terminals 16 - 18 is open.
Output "AL" remains activated (terminals 16 - 17 closed) until the error ceases or until it is confirmed via the “Alarm” key.
- An error is displayed via the red LED "Error message" and on the display.
- The error message signal at output "AL" is deleted after confirming the error via the "Alarm" key.
- The error display can only be deleted once the error has been eliminated.

The following errors activate output "AL" and are displayed if the plant has been equipped with the appropriate contacts:

Summary of Contents for EcoControl DO10

Page 1: ...EcoControl DO10 Desalination and Dosing Controller Operating Instructions...

Page 2: ...dosing medium container empty 8 Programming 8 Menu start 8 Menu selection Selection 8 Input 8 End menu 8 Information Menu 8 Programming 8 Enter password 8 Change password 8 Description of functions an...

Page 3: ...the switching outputs and the total power rating of the plant must not be exceeded The controller should only be used for its specified intended purpose Safety notes Always pay attention to the follo...

Page 4: ...2 17 General Description View of the unit Mains switch Terminal box Internal view F1 Fuse M0 08A F2 Fuse T4A visible type fuse 20 x 5 F3 Fuse M0 2A...

Page 5: ...gger functions via the ENTER key F Arrow keys Use these keys to operate the menu drive in the display and to enter values and programming data G M key Call the menu and return to the submenu levels H...

Page 6: ...ater volumeter remain even during a voltage loss The real time clock is battery buffered and thus keeps on running Confirm the fault display via the Alarm key Error message Des val OPEN You have activ...

Page 7: ...mally open Volt free relay output max load 240 V AC 4 A 16 17 18 AL EV OUT Output alarm input valve c contact Output AL EV nc normally closed Output AL EV no normally open Volt free relay output max l...

Page 8: ...4 one second impulses with a 3 second pause should be provided per 50 litres Litre Impulse 50 0 Impulse duration 1 0sec Impulse pause 3 0sec No of impulses 4 Note The impulse ratio in litres impulse s...

Page 9: ...ination water S Total quantity of additional water S Quantity of evaporation water FC monitoring input desalination valve flow controller Monitors whether the desalination valve is closed and no water...

Page 10: ...menu option via the ENTER key i e you jump into a submenu Call the next menu option via the DOWN arrow key Scroll through the menu this way Input Inputs are only possible in the BASIC PROGRAM menu an...

Page 11: ...olume has been reached Desalination Automatic desalination The water meter impulses are added up After reaching the preset quantity of water start volume in litres sum of impulses x basic number of th...

Page 12: ...tely Dosing You can use the dosing valve or solenoid or motor dosing pumps Select the controller according to the requirements Single impulse For the single impulse The dosing output relay K2 is switc...

Page 13: ...n active flow controller for flow through Diagram of desalination monitoring Output AL EV draining function Program the function EV to activate the Draining function The input valve is closed and the...

Page 14: ...he manual function Auto desalination Press the ENTER key to start desalination with the programmed desalinaton time The menu is exited the operating display Desalination appears and the Desalination l...

Page 15: ...k only continues to run if the unit is switched on Correct if necessary the time and date after a longer period of voltage loss or if the plant has been switched off Anzeige M Service Time Date The di...

Page 16: ...ut are displayed as on inactive statuses as off e g OUTPUT AV or INPUT FC off on Software status Call the current software status here Draining Start the Draining function via the ENTER key The displa...

Page 17: ...4 05 Water meter MANUAL IMPULSES Desalination 12 03 02000 l DESAL TIME mm ss 02 30 START VOLUME Desal time Imp duration Litre Impulse Impulse pause No of impulses FCT EMPTY Norm closed Norm open Delay...

Page 18: ...16 17 Technical appendix Example of a simple circulating coolant Connection example...

Page 19: ...Degree of protection IP54 Protection class I Conformity EN 50081 1 EN 50082 2 EN 61010 1 Ambient temperature 10 45 C Dimensions EcoControl DO10 W x H x D 175 x 165 x 135 mm Weight approx 0 8 kg We res...

Reviews: