Heyl EcoControl DO10 Operating Instructions Manual Download Page 10

8/17

MENU

Service

Information

Basic program

"M"

LL dosing medium container empty

Connect a float switch or similar device here to monitor the dosing medium container.

Enter the desired effect of the contact (active as normally closed or normally open) and set the delay time used for testing
in menu 

"M"

 

º

 Basic Program 

º

 Program Values 

º

 Functions 

º

 Fct. Empty

If, in addition to the error message in the display, the alarm relay should also switch during an empty message, program
the alarm function.
Also enter a delay time to ensure evaluation for bouncing contacts.

Function

Type of Contact

Test Time 

Action

LL

S

Level transmitters input:

Dosing medium container
EMPTY

programmable

normally

closed/normally open

programmable

00 - 99 seconds

S

Error message

S

Entry in error list

S

Continious alarm if programmed

Programming

Menu start

Call the menu via the "M" key.

Menu selection / Selection

The current line position is displayed as a heading in CAPITAL LETTERS. Activate
the selected/displayed menu option via the "ENTER" key, i.e. you "jump" into a
submenu. Call the next menu option via the "DOWN" arrow key: "Scroll" through the
menu this way.

Input
Inputs are only possible in the BASIC PROGRAM menu and in some SERVICE
menu options.

Select a programming step via the “DOWN" and "UP" arrow keys and activate the
input function via the "ENTER" key.
When entering digits, the digit/position to be changed flashes.
Change to the next or previous digit (now flashing) via the "Right" and "Left" arrow
keys. 
Change the value or selection via the "UP" and "DOWN" arrow keys.
Selection functions are marked with a 

T

 if selection is possible. 

Terminate the input function via the "ENTER" key.

Change to the higher-order menu via the "M" key.

End menu

Return to the higher-order menu via the "M" key. After returning from the highest menu level, the unit is once again in the
display function. The controller returns to the normal operating display (automatic menu end) after 2 minutes if 

no

 key is

pressed in the menu.

Information Menu

"M"

 

º

 Information

Request the current settings without entering a password in the information menu.
The information menu is still displayed even if an incorrect password has been entered.

Summary of Contents for EcoControl DO10

Page 1: ...EcoControl DO10 Desalination and Dosing Controller Operating Instructions...

Page 2: ...dosing medium container empty 8 Programming 8 Menu start 8 Menu selection Selection 8 Input 8 End menu 8 Information Menu 8 Programming 8 Enter password 8 Change password 8 Description of functions an...

Page 3: ...the switching outputs and the total power rating of the plant must not be exceeded The controller should only be used for its specified intended purpose Safety notes Always pay attention to the follo...

Page 4: ...2 17 General Description View of the unit Mains switch Terminal box Internal view F1 Fuse M0 08A F2 Fuse T4A visible type fuse 20 x 5 F3 Fuse M0 2A...

Page 5: ...gger functions via the ENTER key F Arrow keys Use these keys to operate the menu drive in the display and to enter values and programming data G M key Call the menu and return to the submenu levels H...

Page 6: ...ater volumeter remain even during a voltage loss The real time clock is battery buffered and thus keeps on running Confirm the fault display via the Alarm key Error message Des val OPEN You have activ...

Page 7: ...mally open Volt free relay output max load 240 V AC 4 A 16 17 18 AL EV OUT Output alarm input valve c contact Output AL EV nc normally closed Output AL EV no normally open Volt free relay output max l...

Page 8: ...4 one second impulses with a 3 second pause should be provided per 50 litres Litre Impulse 50 0 Impulse duration 1 0sec Impulse pause 3 0sec No of impulses 4 Note The impulse ratio in litres impulse s...

Page 9: ...ination water S Total quantity of additional water S Quantity of evaporation water FC monitoring input desalination valve flow controller Monitors whether the desalination valve is closed and no water...

Page 10: ...menu option via the ENTER key i e you jump into a submenu Call the next menu option via the DOWN arrow key Scroll through the menu this way Input Inputs are only possible in the BASIC PROGRAM menu an...

Page 11: ...olume has been reached Desalination Automatic desalination The water meter impulses are added up After reaching the preset quantity of water start volume in litres sum of impulses x basic number of th...

Page 12: ...tely Dosing You can use the dosing valve or solenoid or motor dosing pumps Select the controller according to the requirements Single impulse For the single impulse The dosing output relay K2 is switc...

Page 13: ...n active flow controller for flow through Diagram of desalination monitoring Output AL EV draining function Program the function EV to activate the Draining function The input valve is closed and the...

Page 14: ...he manual function Auto desalination Press the ENTER key to start desalination with the programmed desalinaton time The menu is exited the operating display Desalination appears and the Desalination l...

Page 15: ...k only continues to run if the unit is switched on Correct if necessary the time and date after a longer period of voltage loss or if the plant has been switched off Anzeige M Service Time Date The di...

Page 16: ...ut are displayed as on inactive statuses as off e g OUTPUT AV or INPUT FC off on Software status Call the current software status here Draining Start the Draining function via the ENTER key The displa...

Page 17: ...4 05 Water meter MANUAL IMPULSES Desalination 12 03 02000 l DESAL TIME mm ss 02 30 START VOLUME Desal time Imp duration Litre Impulse Impulse pause No of impulses FCT EMPTY Norm closed Norm open Delay...

Page 18: ...16 17 Technical appendix Example of a simple circulating coolant Connection example...

Page 19: ...Degree of protection IP54 Protection class I Conformity EN 50081 1 EN 50082 2 EN 61010 1 Ambient temperature 10 45 C Dimensions EcoControl DO10 W x H x D 175 x 165 x 135 mm Weight approx 0 8 kg We res...

Reviews: