10.2.2 Misprint
Display
Criterion
Cause / Remedy
Delta-p High
Alarm 1
Pressure exceeds the defined
limit for alarm 1
Delta-p High Alarm 1
too low
sudden influx of dust
Delta-p High
Alarm 2
Pressure exceeds the defined
limit for alarm 2
Delta-p High Alarm
too low
sudden influx of dust
Delta-p Low
Alarm
Pressure is below the defined
limit
Delta-p High Alarm
too low
No throttle cable
Delta-p sensor error
Value corresponds to the
highest or lowest limit
Open line to the
sensor
Short circuit on the
sensor
System pressure
High
Alarm
System pressure exceeds the
defined limit
Compressed air
supply defective
Pressure High Alarm
too low
System pressure sensor
error
Value corresponds to the
highest or lowest limit
Open line to the
sensor
Short circuit on the
sensor
10.2.3 Valve control Bus error
Display
Criterion
Cause / Remedy
Ch. 2 Slave 1 Bus error
No communication with this
control
Line interruption
Voltage supply at the
node is missing
Fuse tripped