10.2 Alarm screens
The red alarm LED indicates pending alarms.
Pressing the alarm key shows the current alarms.
Pressing the alarm key again shows an alarm log list of the last 200 alarms with time. A small
tick behind the alarm number indicates the acknowledgement status.
Actual alarms
Ch. 1 Manifold press 1 Low
Ch. 1 Manifold press 2 Low
Ch. 2 Valve control.
1 Bus-Error
Acknowl.
2: 3
You can switch between the screens with the alarm key.
Alarm protocol
2
17.03.14 10:17:18
Ch. 1 Manifold press 1 low
1 Bus-Error
3 17.03.13 10:17:19
Ch. 2 Valve control
1 Bus-Error
Acknowl.
200
10.2.1 Sensor error
Display
Criterion
Cause / Remedy
Analogue-In sensor break
Analogue-in sensor lock
Analogue input on master open or
short-circuited
Sensor error
Sensor not
connected
System description
does not match
actual hardware.
The alarms that are currently present. If an
alarm cause is eliminated, the message
disappears.
The
hold function
for alarms must not be
switched on (12.7).
A list of all alarms that have occurred, sorted by
time of occurrence.
The most recent alarms are mentioned first. A
maximum of 200 alarms are listed.