HE 5760 Operating Instructions
# 372449 | Version 3.2
35
4.13 Drain valves
0
, 0…2
Number of drain valves per valve slave box.
0 = Drainage function switched off.
Valves from 2 pressure tanks can be connected to one valve box.
Connection sequence at the valve terminals for 2 tanks:
Blow valves Tank1, Blow valves Tank2, Drain valve Tank1, Drain valve Tank2
4.14 Drainage pulse
100.0
, 10.0...60000.0 msec
Opening duration of a drain valve.
4.15 Drainage pause
60.0
, 1.0...10000.0 min
Pause until the next actuation of the same drain valve.
4.16 Start/stop function
static
, dynamic
The type of command (continuous signal, tactile signal).
4.17
1. Parallel valve
no
, 1
...
48
The system is capable of controlling up to 4 valves simultaneously. Each valve that is to be
operated simultaneously has its own parameter. Precondition: Valves to be controlled
simultaneously are not connected to the same valve control unit. The parameter is understood
as an offset value on the valve control unit: e.g. '2' means valve no. 'N' on valve control unit '1'
and valve no. 'N' on valve control unit '3' are controlled together.
4.18
2. Parallel valve
without
, 1...48
as above
4.19
3. Parallel valve
without
, 1...48
as above
9.3.5 Overall cleaning (cleaning process)
5.1 Post cleaning
1
, 0...10 cycles
Post-cleaning is a cleaning procedure with all valves of the filter system. Up to 10
Repetitions of complete cleaning cycles can be selected. The post-cleaning is activated with
the post-cleaning input and uses pulse and pause time of the second control time set.
5.2 Chamber cleaning
1
, 0...10 cycles
Chamber cleaning addresses all valves in a chamber. Up to 10 repetitions of the
Chamber cleaning can be selected.