HE 5731 Operating instructions
31
# 373344, Version 1.5
Parameterisation
The following parameters can only be changed with the "EasyTool Controls" program:
(
see chapter 7.4 Parameterisation with Service PC
Parameter
Adjustment range
Factory
setting
Pre-
assignment
Delta-p filter
Filter constant for damping the
Delta-p measurement.
0.
1…10.0 s
2.0 s
2.0s
Delta-p working range
Defines the working range below
the upper threshold in % of the
measuring range.
Alternative to the lower thresh-
old.
1…100%
10%
10%
High alarm Delay
Delay after the high alarm
threshold has been exceeded
until the high alarm relay is
switched.
0.
1…30.0 s
2.0 s
2.0 s
Low-alarm Delay
Delay after falling below the low
alarm threshold until the low
alarm relay is switched.
The relay is not switched if the
value falls below the final clean-
ing threshold within the delay.
1…600 s
300 s
300 s
Precoating Offset
The precoating offset increases
the start threshold for cleaning
(upper threshold).
At an offset of 0, the precoating
function is disabled.
After reaching the first cleaning
threshold (increased by the pre-
coating), the precoating is auto-
matically disabled.
OFF, 0…500.0 mbar
1.0 mbar
1.0 mbar
3.0 mbar
13.0 mbar
Post-cleaning Offset
The automatic post-cleaning is
activated when the value “Post-
cleaning threshold” + value “Off-
set post-
cleaning” is exceeded
(is independent of the lower
threshold)
0.5…10.0 mbar
2.0 mbar
2.0 mbar
5.0 mbar
10.0 mbar