HE 5731 Operating instructions
30
# 373344, Version 1.5
Parameterisation
Parameter
Adjustment
range
Default
setting
Pre-assignment
Lower threshold [mbar]
If underrun, dp-dependent
cleaning stops.
End of dp cycle
OFF,
0.0…500.0 mbar
10.0 mbar
10.0 mbar
(at 0…35 mbar
measuring range)
25.0 mbar
(at 0…90 mbar
measuring range)
130,0 mbar
(at 0…450 mbar
measuring range)
Low-alarm [mbar]
Threshold for the low alarm
message.
If the value falls below this
value, the relay contact is closed
if the value does not fall below
the post-cleaning threshold
within the low-alarm delay.
OFF,
-
5.0…500.0 mbar
OFF
OFF
(at
0…35 mbar
measuring range
OFF
(at
0…90 mbar
measuring range)
OFF
(at
0…450 mbar
measuring range)
Post-cleaning Threshold
[mbar]
The threshold is activated when
the lower threshold is exceeded
If the threshold is activated and
the pressure falls below the
threshold, a post-cleaning cycle
is triggered and the cleaning re-
lay is closed for the parameter-
ised post-cleaning time.
OFF,
0.0…500.0 mbar
2.0 mbar
2.0 mbar
(at
0…35 mbar
measuring range)
5.0 mbar
(at 0…90 mbar
measuring range)
25.0 mbar
(at
0…450 mbar
measuring range)
dp-Offset [mbar]
The offset is added to the cur-
rently measured differential
pressure.
-
50.0…50.0 mbar
0 mbar
0 mbar
Explosion hazard!
Before opening the housing, make sure that no explosive environmental
conditions, such as dust, exist.
The number of valves is valid for the entire system. The number of valves of each control
unit is set via the valve coding switch (s
ee chapter 6.3.1 Coding
switch). An interruption
alarm goes off, if less valves as indicated are connected.