30
HE 5422 Operating Instructions
# 342338 | Version 1.3
9
Parameterization
9.1
Parameter table
Sensor Min. = Base measuring range start
Sensor Max. = Base measuring range end
Note!
The base measuring range is to be taken from the nameplate!
Note!
Please note that, when setting the measuring range start and end, the
difference between the two must not be less than 25% of the base
measuring range!
The following parameters can be set using the device keyboard (
(
see also section 9.2
Parameterization with device keyboard):
Parameter
Adjustment range
Factory Setting
Unit
Password
Protection against unauthorized
parameter changes.
0…9999
0001
Δp Filter [s]
Filter constant for the
current differential
pressure
0.2
– 60.0
2.0
s
Post-cleaning time [min]
The cleaning relay is
closed for post cleaning
for the configured time.
OFF, 1
– 999
10
min
Δp measuring range [mbar]
Is used to convert the
current differential
pressure into the 4 - 20
mA output signal used.
0 mbar = 4 mA
Upper range value =
20mA (
if this parameter is
set to a negative
measuring range, the
pressure evaluation is
inverted. All
corresponding parameters
are also displayed
negatively.)
Sensor Min…Sensor
max.
Sensor max.
(according to the nameplate)
High-Alarm [mbar]
Threshold for the high
alarm message.
If exceeded, the relay
contact is closed.
OFF, 0…Sensor max.
30.0
mbar