24 

HE 5422 Operating Instructions  
# 342338 | Version 1.3 

 

Symbols/Displays 

 

Meaning 

 

 

 

Operating message 

 

 

Cleaning active 

 

 

Alarms active 

 

 

Differential pressure measurement in pascal 

 

 

Differential pressure measurement in millibar 

 

 

Test & Service 

 

 

 

Filter constant of the differential pressure measurement 
 

 

 

Post-cleaning time 

 

Normal operation: LED lights up when post-cleaning is 
active 

 

Parameterization mode: LED flashes when the parameter 
can be selected

 

 

 

PARA key

 Parameterization mode ON/OFF 

 

 

UP key

: increase the displayed value 

 

 

DOWN key

: decrease the displayed value 

 

 

ENTER 

key: accept the displayed value 

 

 

Display: 

 

Normal operation: current differential pressure 

 

Parameterization mode: Parameter values 

 

Alarm notices

 

 

 

Run 

 

Lights up continuously when there is a supply voltage. 

 

 

Status 

 

Lights up permanently when there is communication 
between the control system and operating unit. 

 

Flashes when waiting for communication between the 
control system and operating unit. 

 

Flashes rapidly when the boot loader (start-up program) is 
running. 

 

 

Error

 

 

Is linked to the alarm / operation relay of the software. 

 

LED lights up when the relay drops out (alarm message). 

 

LED goes out when the relay picks up (operation).

 

 
 

 

Summary of Contents for HE 5422

Page 1: ...342338 Version 1 3 Differential pressure regulator HE 5422 HE 5422 HD Operating Instructions Translation of Original German version...

Page 2: ...ed by HESCH Industrie Elektronik GmbH Documentation Department Copyrights Copyright 2021 HESCH Industrie Elektronik GmbH All rights reserved The content including pictures and the design of these oper...

Page 3: ...1 Section 6 1 Read and set password added section 10 images adapted section 12 Accessories removed section 13 ordering information added section 6 2 Supply voltage revised Bg 25 02 2021 1 2 Chapter 3...

Page 4: ...D SET PASSWORD 20 6 2 SUPPLY VOLTAGE 21 6 3 INPUTS 22 6 4 OUTPUTS 22 6 4 1 Relay 22 6 4 2 Analogue output 22 6 5 MEASURING HOSE ASSEMBLY AT THE PRESSURE CONNECTION 22 7 DISPLAY AND CONTROL ELEMENTS 23...

Page 5: ...tted in this manual The manufacturer is not liable for improper use and any resulting personal injury or material damage the risk is borne solely by the user Failure to comply with the above criteria...

Page 6: ...verity of the danger is indicated by the respective signal word Explosive atmosphere warning sign High Voltage Warning Warning of material damage caused by electrostatic charge Property Damage Warning...

Page 7: ...tion Danger of Electrocution Never open the device when live Live parts can be exposed when the devices are opened or covers and parts are removed Junction points can also be live Danger of Electrocut...

Page 8: ...ice is to be decommissioned Secure the device against unintentional operation If the device is interconnected with other devices and or systems consider any potential effects before switching off and...

Page 9: ...se in zone 22 for dust IP65 Protection type dust tight and protected against water jets The following special regulations must be observed The cables must be correctly inserted through the cable ducts...

Page 10: ...FSO T 25 C Total error 2 FSO T 0 60 C 1 5 FSO T 0 60 C 1 0 FSO T 0 60 C Connection type pneumatic HE 5422 2 x Schott push in fittings for 6 mm hose outer diameter HE 5422 HD 2 x Schott push in fitting...

Page 11: ...ble gland HE 5422 2 M25 with multiple sealing insert for 3 lines of diameter 7mm HE 5422 HD 2 M25 with multiple sealing insert for 3 lines of diameter 7mm nickel plated brass Environmental Conditions...

Page 12: ...ations for use in EX ATEX zones must be observed see section 2 3 Safety in the individual operating phases Note A drilling template can be found on www hesch de When printing please make sure that the...

Page 13: ...7 mm for HE 5422 HD Dimensions HE 5422 HD die cast aluminium housing Scope of Delivery HE 5422 HE 5422 HD differential pressure regulator Operating Instructions Note Check the delivery for completenes...

Page 14: ...e Open the case cover to the left up to an angle of 105 Note Make sure to move the screwdriver to the right to prise the hinge open see Figure 3 If the screwdriver is moved to the left the housing cov...

Page 15: ...the right side of the housing After opening loosen the two screws see Figure 4 with a screwdriver bit size Tx 20 and tighten again when closing the device Open HE 5422 HD housing Note When closing the...

Page 16: ...Version 1 3 4 3 Mounting the device 4 screws are required to fasten the device to the wall Not included in the scope of delivery Rear of housing Alternative Wall mounting with wall brackets for more...

Page 17: ...HE 5422 Operating Instructions 342338 Version 1 3 17 5 Device Description 5 1 Summary of device versions 5 1 1 HE 5422 with polycarbonate housing Front view HE 5422 with polycarbonate housing...

Page 18: ...18 HE 5422 Operating Instructions 342338 Version 1 3 5 1 2 HE 5422 HD with die cast aluminium housing Front view HE 5422 with die cast aluminium housing...

Page 19: ...for the use of the device must be observed before and during operation The protective conductor connection in the corresponding device carrier must be conductively connected to the protective conduct...

Page 20: ...password The factory set password is displayed on delivery see also 9 1 Parameter table 2 Press the ENTER key to set a new password 3 The first digit starts to flash Set the desired value using the U...

Page 21: ...2 HD Otherwise the device is not earthed Note Either 100 240 VAC or 24 VDC must be connected Inside view 1 Open the housing as described in section 4 2 Opening the device 2 Connect existing supply vol...

Page 22: ...6 4 Outputs 6 4 1 Relay The device has 4 potential free relay outputs The contacts can each be loaded with 250 VAC 5 A 6 4 2 Analogue output The current differential pressure is reported with a non ga...

Page 23: ...HE 5422 Operating Instructions 342338 Version 1 3 23 7 Display and control elements External display and control elements Internal display elements on the PCB Status LED on p module...

Page 24: ...crease the displayed value DOWN key decrease the displayed value ENTER key accept the displayed value Display Normal operation current differential pressure Parameterization mode Parameter values Alar...

Page 25: ...n The LEDs are used in normal operation to display the differential pressure In parameterization mode the selected parameter value is indicated by the respective LED flashing Delta p measuring range H...

Page 26: ...y to select the desired test function a e a Display of digital inputs start postcl hold i off1 on Shows the status of the start signal Shows the status of the post cleaning signal Shows the status of...

Page 27: ...point of the display flash 7 Press the PARA key to save the entry 8 2 Differential pressure measurement Figure 13 shows the pressure connections using the example of the device variant with polycarbo...

Page 28: ...shold is exceeded and ended when the lower cleaning threshold is reached There is a delay time of 5 minutes in order to carry out post cleaning in a normal switch off process without triggering an ala...

Page 29: ...ure unit from pascal to mbar or vice versa The set unit is shown below the 7 segment display LED or lights up 8 3 2 Activate deactivate precoating and 1 Press the UP and ENTER keys simultaneously to a...

Page 30: ...g Unit Password Protection against unauthorized parameter changes 0 9999 0001 p Filter s Filter constant for the current differential pressure 0 2 60 0 2 0 s Post cleaning time min The cleaning relay...

Page 31: ...low alarm message If the value falls below the limit the relay contact is closed unless the post cleaning threshold is undershot within the low alarm delay OFF 5 0 Sensor max OFF Post cleaning thresho...

Page 32: ...till held after the hold signal disappears 0 999 5 s Maximum hold time Maximum time for which the differential pressure is recorded 0 999 30 s p working range Defines the working range below the upper...

Page 33: ...it BG cleaning time s Duration of background cleaning 1 3600 300 s Note The threshold values can be set as desired There is no logical check If the values of the lower thresholds are parameterized via...

Page 34: ...in the parameter menu the password does not have to be entered again and 6 Use the UP and DOWN keys to select the desired parameter The current value is shown on the display 7 Press the ENTER key to c...

Page 35: ...files or data Instructions for the most important program functions are available from HESCH 9 4 Offset for zeroing Should a zeroing need to be carried out a warm up time of 30 minutes must be observe...

Page 36: ...3 After 5 seconds codE appears to prompt entry of the password 4 Press the ENTER key to start entering the password 5 After entering and confirming the last digit of the password the control system s...

Page 37: ...0 1 Normal operation Operation is started by applying the supply voltage The system is controlled via the differential pressure and the inputs of the device Note All digital inputs of a system refer t...

Page 38: ...following causes lead to an error message see section 11 Error messages 1 Power failure 2 Device fault parameter error 3 p sensor error measuring range exceeded Cleaning relay The cleaning relay is c...

Page 39: ...HE 5422 Operating Instructions 342338 Version 1 3 39 The current output is not galvanically isolated 0 10 V 0 4 20 mA GND...

Page 40: ...he hold signal expires again i e the edge falls again the differential pressure that is used is only used for the differential pressure value that has been set after the adjustable hold time after run...

Page 41: ...eaded connection The differential pressure display shows and the high and low alarm LEDs flash alternately Fault in p module The yellow status LED on the p module does not light up p module is not ins...

Page 42: ...n 1 3 Display LED Cause Remedy Alarm LED flashes No communication with I O unit Check the connection cable between the I O unit and the control unit for damage Possibly the RJ 45 connector is not prop...

Page 43: ...he device Disposal Dispatch metals and plastics for recycling The electrical and electronic components must be collected separately and disposed of accordingly Dispose of assembled PCBs in a proper ma...

Page 44: ...44 HE 5422 Operating Instructions 342338 Version 1 3 13 Declaration of conformity...

Page 45: ...HE 5422 Operating Instructions 342338 Version 1 3 45...

Reviews: