10
102 (e.g. if “24” is set as the Parameter value, it means the second relay and fourth relay will never be ON at the
same time).
Note:
In this mode both relays cannot be switched ON simultaneously and first one relay switches OFF, then
another switches ON.
Tip:
This function can be used for motors direction control.
10)
ROLLER SHUTTER:
When two relays are connected to the same button and are Inverse Mode, they will
operate in ‘roller shutter’ mode. After entering this mode, relays will switch to OFF state, and never switch ON
simultaneously. The relay behavior is as follows for this four-touch cycle (in this order):
•
1
st
press: the first relay will be switched ON and the second relay will be switched OFF
•
2
nd
press: both relays will be switched OFF
•
3
rd
press: the second relay will be switched ON and the first relay will be switched OFF
•
4
th
press: both relays will be switched OFF
Tip:
This can be used to control motor directions with one button only.
Each touch button can also be used to run scenarios or change modes in the connected gateway or associated devices.
3. Each button’s backlight can be configured as follows to indicate:
a) Relay output state
b) Touch button state
c) Mode state in connected gateway
d) Associated device state
Note:
It is possible to choose the light color for each state: red for ON and blue for OFF, or blue for ON and red for OFF
(see Parameter 30 settings).
If the HE-TPS04 is included to the Z-Wave gateway, the scene controller, light, temperature & humidity sensors info,
and eight binary switches will appear. The scene controller indicates which button was pressed, held, or released and
allows the running of scenes on the Z-Wave gateway. The first four binary switches indicate and control the button
backlight. The remaining four binary switches indicate and control the relay output.
Settings (available through Z-Wave network)
All configuration parameters are accessed through Z-Wave COMMAND_CLASS_CONFIGURATION
Parameters List & Factory Defaults
Number
Size
Description
Default
Value
Available Values
1
1 byte
Frequency Region
Read
Only
0 … 9
2
Reserved by the manufacturer
3
4 bytes
Hardware and Software Versions
Read
Only
XXYYZZ
4
4 bytes
Energy Consumption, kW
Read
Only
Total
consumption
5
1 byte
Backlight brightness control
0
0, 1 … 10
6
1 byte
Touch buttons sensitivity. 1 = Lowest; 10 = Highest
6
1 … 10
7
1 byte
Relay 1 output NO or NC mode
0
0, 1
8
1 byte
Relay 2 output NO or NC mode
0
0, 1
9
1 byte
Relay 3 output NO or NC mode
0
0, 1
10
1 byte
Relay 4 output NO or NC mode
0
0, 1
11
Reserved by the manufacturer
12
2 bytes
Power of the Relay 1 load in W
0
0…1100
13
2 bytes
Power of the Relay 2 load in W
0
0…1100
14
2 bytes
Power of the Relay 3 load in W
0
0…1100
15
2 bytes
Power of the Relay 4 load in W
0
0…1100