OPERATING INSTRUCTIONS TREND SERIES
TLG Unit Voltage Checks
-9 pin connector located under “Do Not Remove” plate, upper LH Corner
Pin
Satisfactory
Voltage
Range
Brown
-3.8
to
-4.2
volts
Red
-3.8
to
-4.2
volts
Orange
+3.8
to
+4.2
volts
Yellow
-11.5
to
-12.5
volts
Green
+11.5
to
+12.5
volts
Blue
+3.8
to
+4.2
volts
Grey
0 volts
White
+4.75 to +5.25 volts
Miscellaneous Troubleshooting Specifications
HT-400
Sensor
Ohm
Readings
Green - Black
350 ohms
Red
-
White
350
ohms
All other color combinations
266 ohms
All
color
to
Ground
open
Shield
to
Ground open
M