13
SERVICE REMINDER
STEP 21S
– Set scheduled service display using
or
buttons. Available options are OFF, TIME, ON GAL
or BOTH. Selecting OFF disables this feature. If OFF is selected, press NEXT to exit System Setup. If
TIME, ON GAL or BOTH is selected press NEXT to select the TIME and/or ON GAL values. See Steps 24S
and/or 25S. This can also activate relay if Service Alarm is selected on Step 19S. Press REGEN to return
to the previous step.
STEP 22S
– Service alarm for TIME ranges from 0.25 to 9.75 years. Use
or
buttons to select length
of time between service reminders. Press NEXT to either exit System Setup or if BOTH was selected go
to Step 23S. Press REGEN to return to the previous step. When time selected and # of days drops below
1 year, the next display will show “scheduled service in XXX days” after screen where service reminder is
programmed.
STEP 23S
– Service alarm for ON GAL ranges from 100 to 9,999,000 gallons. Hold
or
buttons until
display flashes “SET” before releasing to select values. Press NEXT to see “Gallons until service” displays.
Press NEXT to exit system. Press REGEN to return to the previous step.
Reset service reminder by holding down up and down arrows together when reminder is displayed.
SERVICE ALARM
➔
SET
BOTH
STEP 21S
SCHEDULED SERVICE
➔
SET
0.25
STEP 22S
SCHEDULED SERVICE
➔
SET
80000
STEP 23S
YR
GAL
RETURN TO NORMAL MODE
RELAY 1 SET POINT
➔
SET
1
GAL
STEP 17S
RELAY 1 DURATION
➔
SET
0:01
MIN
STEP 18S
RELAY 1 SERV ALARM
➔
SET
TRIGGER
STEP 19S
RELAY 2 TRIGGER
➔
SET
REGEN
GAL
STEP 20S
STEP 19S
If Service Alarm chosen to activate relay,
relay closes whenever Service Alarm has triggered.
Programming for relay closure on service reminder is done on Step 24S. Relay opens when
service alarm reset. Press NEXT to go to Step 20S to set Relay 2 Settings. If off selected for
Relay 2, Press NEXT to go to step 22S for service reminder programming.
• Relay closes on Gallons
• Relay closes on Time
• Relay closes on Both
• Off
STEP 20S –
Relay 2 programming includes identical options as Relay 1 with the addition of the ability
to trigger Relay 2 in Error Mode. Relay closes when ever control enters Error Mode and immediately
deactivates when error resolved and control reset. Press NEXT to go to Step 21S.
STEP 17S –
Use up and down arrows to select number of gallons per relay activation of regen
gallon setting. Range: 1 -100 gallons. Press NEXT to go to Step 18S.
STEP 18S –
If Off or Time was selected in previous steps, this screen does not appear. Use up
and down arrows to set duration of relay activation in minutes. Range = 1 second - 500 minutes.
Press NEXT to go to Step 19S. Press REGEN to return to previous step. Meter does not read
during regeneration.