2. Detection range
7.4 Functional description Fan unit ELS-VF.. with automatic humidity control
With integrated, electronic, humidity curve-dependent automatic control unit. If 70 % relative humidity is exceeded or
a rapid increase in humidity, the fan will be automatically activated (always at the highest stage for multi-speed types).
Once the normal room air humidity is achieved, the fan will deactivate again. Regardless of the humidity control unit,
the fan can be activated with an external switch (possibly connected to light) with approx. 45 sec. start-up delay and
approx. 15 minute overrun time.
Factory settings:
Start-up delay: 45 sec., overrun time: 15 min.
Threshold humidity: 70/60 %
X-Y Darstellung (kartesisch)
X
5m
5m
2.5m
2.5m
50°
50°
0°
Draufsicht
Y
5m
5m
2.5m
2.5m
41°
41°
0°
Seitenansicht
Y/m
Meßfeld
1
(Max. 7.42m)
(Max. 5.66m)
X/m
2
2
3
3
4
4
1
1
1
2
2
3
3
Hinweise: 1. Das x-y-Diagramm zeigt die Meßbereiche (projeziert auf die x-y-Ebene)
2. Die unterschiedlichen Muster zeigen die Meßbereiche der 5 optischen
Achsen mit den 16 Linsen. Ein Objekt, dessen Eigentemperatur sich von
der Hintergrundtemperatur unterscheidet, und sich von einem Meßfeld
zum anderen bewegt, wird sicher erkannt.
Fig.23
Quelle: Panasonic
Fig.24
Werkseinstellungen bei der Auslieferung:
DIP-Schalter
1
2
3
4
5
6
Auslieferung
on
on
off
off
off
off
DIP-Schalter
Wert
1
2
3
4
5
6
Einschalt-
Verzögerung
0 sec
off
Einschalt-
Verzögerung
45 sec
on
Nachlaufzeit
6 min
off off
Nachlaufzeit
10 min
off on
Nachlaufzeit
15 min
on off
Nachlaufzeit
21 min
on on
Schaltschwelle Feuchte
Ein/Aus
70/60%
rF
off off
Schaltschwelle Feuchte
Ein/Aus
90/80%
rF
off on
Schaltschwelle Feuchte
Ein/Aus
80/70%
rF
on off
Schaltschwelle Feuchte
Ein/Aus
60/50%
rF
on on
Kleine Drehzahl ohne
Zeitfunktion
off
Alle Schaltereingänge
mit Zeitfunktion
on
Fig.25
DIP switch
Circuit board
13
Fan Unit ELS-V..
Installation and Operating Instructions
EN
Factory settings upon delivery
DIP switch
Delivery
DIP switch
Start-up delay
Start-up delay
Overrun time
Overrun time
Overrun time
Overrun time
Humidity switching threshold
On/Off
Humidity switching threshold
On/Off
Humidity switching threshold
On/Off
Humidity switching threshold
On/Off
No speed without
timer function
All switch inputs with
timer function
Value
Plan view
Side view
X-Y representation (Cartesian)
Detecion field
Note: 1. The x-y diagram shows the deteciton field (project on the x-y plane)
2. The differfent patterns show the detection areas of the 5 optical axes
with the 16 lenses. A object with an intrinsic temperature that differs
from the background temperature and moves from one detection field
to another will certainly be detected.