TIP!
2 .9 Functional layout
2 .10 Initial commissioning and adjustment
Useful hint for adjustment!
The adjust ment by means of pressure measurement is explained in the Helios practical workshops, and this is the
easiest way to adjust a KWL EC 500 W ET R/L. In this respect, a pressure measuring connector must be mounted to
each connecting socket/ventilation pipe (approx. 20 cm past the unit connection), and the pressure hoses must be
readily accessible.
To balance the whole system, supply and extract openings should be provided with adjustable elements or valves
(accessories). During extraction of polluted extract air, a filter (accessories) is to be connected. The installation of kitchen
hoods to the system (cause: dirt, fire danger, hygiene) is not permitted. To ensure air circulation within the room suffi-
cient overflow openings (door gap, door grilles) are to be planned.
Any fire regulations must be observed!
Detailed information on the adjustment of KWL wall-mounted units can be found in the Installation and
Operating Instructions “KWL easyControls Initial Commissioning”; No . 82 237!
NOTE
m
9
Compact wall-mounted units KWL EC 500 W ET R/L
Installation and Operating Instructions
2
T4
T3
T1
T2
2
1
1
5
1
T6
Externe Fühler
(Raumseitige Installation)
CO2-Fühler
•
Feuchte/Temperaturfühler
•
VOC-Fühler
•
Fortluft
Zuluft
Abluft
Außenluft
Bei Verwendung eines Heizregisters, muss das Rohrsystem 0,5m vor und nach dem Heizregister
mit temperaturbeständigem bzw. nicht brennbarem Rohr versehen werden (z.B. Wickelfalzrohr)
Abb. KWL EC 500 W Rechts
(T7)
Rücklauf
WW-Register
3
F-AB
Elektrische Nachheizung Type: EHR-R 2,4/160 (Zubehör)
Hinweis: Beim EM-Modul ist im Lieferumfang ein KWL-LTK enthalten
Alternativ:
Warmwasser Nachheizung Type: WHR 160 (Zubehör) mit Hydraulikeinheit
Pos.
Benennung
T1
Außenluftfühler
T2
Zuluftfühler
T3
Abluftfühler
T4
Fortluftfühler
T6
Kanalfühler Type: KWL-LTK (Zubehör)
T7
Frostschutzfühler Type: KWL-LTK (Zubehör) für WW-Register Rücklauf
F-AB
Feuchtefühler intern
Externe
Fühler
CO2-Fühler : KWL-CO2 (Zubehör)
Feuchte/Temperaturfühler: KWL-FTF (Zubehör)
VOC-Fühler : KWL-VOC (Zubehör)
1
Temperaturbeständiges bzw. nicht brennbares Rohr (z.B. Wickelfalzrohr)
2
Iso-Pipe Rohr 160
3
Verbinder mit Dichtung für Geräteanschluss ans Rohrsystem: RVBD 160 K
RVBD 180/160
4
Elektrische Vorheizung intern: KWL EVH 500
5
Fig .26
EN
Abb. KWL EC 500 W ET Rechts
Supply air
Exhaust air
Outside air
Extract air
External sensor
(interior installation)
CO2 sensor
Humiditytemp. sensor
VOC sensor
Return
HW register
Fig. KWL EC 500 W ET right
Description
Outside air sensor
Supply air sensor
Extract air sensor
Exhaust air sensor
Duct sensor type KWL-LTK (accessories)
Frost protection sensor type KWL-LTK (accessories) for HW register return
Humidity sensor internal
CO2 sensor KWL-CO2 (accessories)
External
sensors
Humiditytemp. sensor KWL-FTF (accessories)
VOC sensor KWL-VOC (accessories)
Temperature-resistant or non-combustible ducting (e.g. spiral duct)
Iso-Pipe ducting Ø125
Connector with seal for unit connection to duct system.
RVBD 160 K
RVBD 180/160
Electrical pre-heater internal KWL EVH 500
Electrical auxiliary heater type EHR-R 2,4/16 (accessories)
Note: KWL-LTK included in delivery for EM module
Alternative: Hot water auxiliary heater type WHR 160 (accessories) with
hydraulic unit
When using a heater battery, the duct system must be fitted with temperature-resistant
or non-combustible ducting 0.5 m before and after the heater battery (e.g. spiral duct)