TIP!

 

– Filter

 

The KWL compact unit is equipped with fine filters on the outside and extract air side as standard (DIN EN 13779):

 

• Outside air/extract air

:

 

Repl. air filter F5 Extract air 1pc.      ELF-KWL 700 D/5  VDI 

No. 4189

  

 

Repl. air filter F7 Supply air 1pc. 

ELF-KWL 700 D/7 VDI 

No. 4191

    

 

Repl. air filter F5 Extract air 1pc.      ELF-KWL 1400 D/5 VDI 

No. 4193

  

 

Repl. air filter F7 Supply air 1pc. 

ELF-KWL 1400 D/7 VDI 

No. 4195

    

 

Repl. air filter F5 Extract air 1pc.      ELF-KWL 2000 D/5 VDI 

No. 4197

  

 

Repl. air filter F7 Supply air 1pc. 

ELF-KWL 2000 D/7 VDI 

No. 4204

    

The internal pressure-dependent filter monitoring system signals the necessty of inspection and cleaning or 
filter replacement on the controller. Irrespective of this, a 3-month inspection is recommended. They must be 
exchanged for hygiene reasons after one year of operation at the latest. If the filters are damp or mouldy, they 
must be exchanged immediately.

 

Replacement air filters are also available online at 

www.ersatzluftfilter.de

!

6.3  Reset function

The manual reset takes place by pressing the reset lever (Fig.26), which is located directly on the electrical pre-heater.
Proceed as follows:

The unit must be must be disconnected from the power supply before any maintenance and installation work 
or before opening the terminal compartment!

1. Turn lid (1) and open “outside air” inspection flap 

2. Pull both filter locks downwards

3. Remove outside air filter 

 

4.  Press down reset lever

5. Subsequently re-insert outside air filter. Pay attention to air direction arrows

!

 

6. Close inspection flap and reconnect ventilation unit to power supply. 

NOTE

 

+

26

Central ventilation units KWL EC.. D Pro/WW

Installation and Operating Instructions

Fig.23

Fig.24

(1)

Fig.26

Fig.25

 

EN

Summary of Contents for KWL EC 1700 D Pro / WW

Page 1: ...ilatoren MONTAGE UND BETRIEBSVORSCHRIFT Zentral L ftungsger te f r Deckeninstallation KWL EC 700 D Pro WW KWL EC 1400 D Pro WW KWL EC 2000 D Pro WW Mit W rmer ckgewinnung und EC Technik f r Be und Ent...

Page 2: ...nd Akkus im Handel oder in kommunalen Sammelstellen unentgeltlich zur ckgeben Batterien oder Akkus die Schadstoffe enthalten sind mit dem Symbol einer durchgekreuzten M lltonne gekennzeichnet Unter de...

Page 3: ...Heizregister Seite 10 3 2 6 Behaglichkeitstemperatur Seite 11 3 2 7 Verschlussklappen Seite 11 3 2 8 RUN Ausgang Seite 11 3 2 9 Externer Kontakt Seite 11 3 2 10 Brandmodus Seite 11 3 2 11 Kondensat K...

Page 4: ...ernehmens veranlassen Bei nicht fristgerechter Reklamation gehen evtl Anspr che verloren 1 5 Einlagerung Bei Einlagerung ber einen l ngeren Zeitraum sind zur Verhinderung sch dlicher Einwirkungen folg...

Page 5: ...bestellt werden ber das Nachheizregister kann eine konstante Zuluft bzw Raumluft realisiert werden 1 9 Leistungsdaten Zum Erreichen der vorgesehenen Leistung ist ein ordnungsgem er Einbau und korrekt...

Page 6: ...Nachheizung Ausgang kW Elektrische Zuleitung bis UV NYM J F rderleistungen Vm3 h 1000 650 400 KWL EC 1400 D Pro WW Spannung Frequenz 3N 400 V 50 Hz Anschluss nach Schaltplan SS 1007 Nennstrom L ftungs...

Page 7: ...vermeiden muss je nach Bausubstanz bauseits eine geeignete Schallentkopp lung vorgesehen werden 7 Die Aufstellung des KWL Kompaktger tes darf nur in frostfreien R umen erfolgen da die Gefahr des Einf...

Page 8: ...en Au en Fortluft Zuluftverteiler Abluftsammler ist DN KWL EC 700 D 250 mm KWL EC 1400 D 315 mm KWL EC 2000 D 400 mm oder dementsprechender Kanal vorzuse hen f r Stichleitungen wird der entsprechend r...

Page 9: ...VDE 0100 sowie die TAB der EVUs sind unbedingt zu beachten Ein allpoliger Netztrennschalter Revisionsschalter mit mindestens 3 mm Kontakt ffnung VDE 0700 T1 7 12 2 EN 60335 1 ist zwingend vorgeschrieb...

Page 10: ...WW Ger tetypen Twater Frostschutzf hler WW Heizregister R cklauf nur bei WW Ger tetypen Ext 3 Kanalf hler Lieferumfang L ftungsger t Panel Komfortbedienelement mit integriertem Temperaturf hler inkl...

Page 11: ...er ist mit zwei STB Sicherheitstemperaturbegrenzern ausger stet die STB auto Reset Ausl se temperatur 50 C und manuellem Reset Ausl setemperatur 120 C sind in Reihe angeschlossen Sobald ein STB Begren...

Page 12: ...ern Anschluss und Regelung des externen Warmwasser Nachheizregisters nur Type KWL EC D Pro Bei den Ger tetypen KWL EC 700 1400 2000 D Pro ist es m glich ein externes Warmwasser Nachheizregister ein zu...

Page 13: ...L ftungsmodus zu versetzen 3 2 10 Brandmodus Fire Kontakt ber die Funktion Brandmodus Fire Kontakt kann das KWL Ger t in zwei Betriebszust nde Abluftbetrieb oder Stand by Modus versetzt werden Ger t...

Page 14: ...um geleitet W rmer ckgewinnung inaktiv indirektes K hlen der Raumluft Wann wird der Ger tebypass genutzt Der Bypass wird vorwiegend in den Sommermonaten zur sogenannten Nachtk hlung genutzt Bei der Na...

Page 15: ...L ftungs ger t f r eine definierte Zeitspanne mit 100 der Ventilatorleistung Als Ergebnis der Ventilatorkalibrierung wird der maximal erreichbare Volumenstrom und der entsprechende statische Druck im...

Page 16: ...etriebsvorschrift 4 0 Aufputz Komfortbedienelement mit Touchscreen Das Zentral L ftungsgerger t wird mit einem Aufputz Komfortbedienelement angesteuert Abb 11 Es erm glicht frei definierbare Betriebst...

Page 17: ...um die gew nschten Zeitintervalle einzugeben Es k nnen bis zu vier Zeitintervalle f r jeden Wochentag programmiert werden Beispiel Zeitintervall 1 Zeitintervall 2 Zeitintervall 3 Zeitintervall 4 5 Zu...

Page 18: ...pie auf Wochentage bertragen Beispiel Programmierung eines Tagesprogramms 1 Die Taste Ein ausw hlen Tagesprogramm ist aktiv 2 Die Taste Tag ausw hlen um das Tagesmen zu aktivieren 3 Die Taste 1 4 dr c...

Page 19: ...rs Werkseinstellung Zuluftsensor eingeben 3 Mit Taste RETURN zur ck ins Hauptmen Hauptmen Temperaturwert 8 Helligkeit Kontrast Ton 1 Im Hauptmen die Taste Helligkeit Kontrast dr cken 2 Helligkeits und...

Page 20: ...rh ht bzw reduziert das L ftungsger t daher die Volumenstromleistung in Abh ngigkeit des Ist Grenzwert Abgleichs Durch erneutes Dr cken auf das A Symbol gelangt man wieder in den L ftungsmodus manuell...

Page 21: ...cemen Servicemen PIN Servicemen 4 Startmodus 1 Im Servicemen die Funktion Startmodus ausw hlen mit OK best tigen 2 Taste L fter dr cken und gew nschten Volumenstrom einstellen 3 Mit Pfeiltasten die Mi...

Page 22: ...s 2 Auf das Anzeigefeld dr cken um zur ck ins Servicemen zu gelangen Servicemen Anzeige Funktionstest Funktionstest Servicemen 10 Ext F hler 1 Im Servicemen die Funktion Ext F hler ausw hlen mit OK be...

Page 23: ...dmodus 1 Im Servicemen die Funktion Brandmodus ausw hlen mit OK best tigen 2 Taste Ger t aus ausw hlen das Ger t schaltet im Brandfall aus 3 Taste Abluft ausw hlen der Abluft Ventilator wird im Brandf...

Page 24: ...ftungsger te KWL EC D Pro WW Montage und Betriebsvorschrift Zus tz Servicefunktion Symbolerkl rung 1 Volumenstrom Abluft Ventilator 2 Volumenstrom Zuluft Ventilator 3 Zuluft Au enlufttemperatur Ext 1...

Page 25: ...PITEL 5 ABMESSUNGEN KENNLINIEN DE a A J m n n m F E E B I b z y x Z Y X h H K k Ansicht Revisionsseite unten d c C D B b A a H h J I K k c KWL EC 700 D 957 840 1418 1400 359 350 900 872 336 45 300 KWL...

Page 26: ...Ger t allpolig vom Netz zu trennen Gef hrdung durch elektrischen Schlag bewegliche Teile Gebl se und hei e Oberfl chen 6 1 Kreuzgegenstrom W rmetauscher entnehmen reinigen m VERLETZUNGSGEFAHR Durch h...

Page 27: ...cm der D se zu den Lamellen m Max Wassertemperatur 60 C m Die Lamellen nicht umknicken m W rmetauscher beidseitig reinigen m W rmetauscher vor Einbau austrocknen lassen 6 2 Filterwechsel Die Revision...

Page 28: ...er aus hygienischen Gr nden ausgetauscht werden Sind die Filter feucht oder mit Schimmel besetzt m ssen diese sofort ausgetauscht werden Ersatzluftfilter k nnen auch im Internet unter www ersatzluftfi...

Page 29: ...bedienbar 6 6 Zubeh r WHSH HE 24V 0 10V Best Nr 8318 Temperatur Regelsystem f r Warmwasser Heizregister KWL S 700 D Best Nr 4206 bergangsst ck symetrisch KWL S 1400 D Best Nr 4207 bergangsst ck symet...

Page 30: ...chalter VDE 0700 T1 7 12 2 L1 N PE 2 15V GND1 CO2 24V 0 10V 5 Au enluft Verschlussklappe 230V externe Komponente N open auf 230V 230V N open auf 230V 230V 19 40 41 42 43 44 45 47 N 230V 48 49 Kondensa...

Page 31: ...l potentialfreier Kontakt 50 51 Externes Signal potentialfreier Kontakt 52 53 max 50m 4 11 Klemmleiste Platine Platine 250V 2A AC1 UX1 GND2 GND2 WW Type 3 20 GND 0 10V 21 oder KWL EC CO Art Nr 9988 2...

Page 32: ...Kontakt 52 53 max 50m 4 11 Klemmleiste Platine Platine 250V 2A AC1 UX1 GND2 GND2 WW Type 3 20 GND 0 10V 21 oder KWL EC CO Art Nr 9988 2 KWL EC FF Art Nr 9989 KWL CO Art Nr 4272 KWL FTF Art Nr 4273 KWL...

Page 33: ...31 Zentral L ftungsger te KWL EC D Pro WW Montage und Betriebsvorschrift DE 7 3 Verdrahtungsplan KWL EC 700 D Abb 34...

Page 34: ...T 3 T INT 1 T INT 2 T WATTER T ALARM BU GN WH OG RD PK BN Farbcode nach IEC 757 BK sw schwarz black BN br braun brown RD rt rot red OG or orange orange YE ge gelb yellow GN gn gr n green BU bl blau bl...

Page 35: ...1 T INT 2 T WATTER T ALARM BU GN WH OG RD PK BN Farbcode nach IEC 757 BK sw schwarz black BN br braun brown RD rt rot red OG or orange orange YE ge gelb yellow GN gn gr n green BU bl blau blue VT vi v...

Page 36: ...Mesnil Cedex CH HELIOS Ventilatoren AG Tannstrasse 4 8112 Otelfingen GB HELIOS Ventilation Systems Ltd 5 Crown Gate Wyncolls Road Severalls Industrial Park A HELIOS Ventilatoren Postfach 854 Siemensst...

Page 37: ...toren INSTALLATION AND OPERATING INSTRUCTIONS Central ventilation units for ceiling installation KWL EC 700 D Pro WW KWL EC 1400 D Pro WW KWL EC 2000 D Pro WW with heat recovery and EC technology for...

Page 38: ...point or return them to the place where you bought them free of charge Batteries or accumulators that contain harmful substances are labelled with the symbol of a crossed out waste bin The chemical s...

Page 39: ...stream hot water heater battery Page 10 3 2 6 Thermal comfort temperature Page 11 3 2 7 Back draught shutters Page 11 3 2 8 RUN output Page 11 3 2 9 External contact Page 11 3 2 10 Fire mode Page 11 3...

Page 40: ...ged please notify carrier immediately In case of delayed notification any possible claim may be void 1 5 Storage When storing for a prolonged time the following steps are to be taken to avoid damaging...

Page 41: ...E 24 V 0 10 V accessories Ref no 8318 must be ordered separately Constant supply air and or room air can be introduced with the auxiliary heater 1 9 Performance data The unit must be installed correct...

Page 42: ...esign IP20 Aux heater outlet kW Electrical supply line to UV NYM J Air flow rates Vm3 h 1000 650 400 KWL EC 1400 D Pro WW Voltage Frequency 3N 400 V 50 Hz Wiring diagram SS 1007 Rated current ventilat...

Page 43: ...coupling must be provided on site depending on the building material 7 The assembly of the KWL compact unit must only take place in rooms that are free of frost as there is a danger of freezing The ro...

Page 44: ...315 mm KWL EC 2000 D 400 mm or the corresponding duct is to be provided and the is reduced accordingly for branch lines Outside and outgoing air pipes are to be insulated in an appropriate way to red...

Page 45: ...ns switch isolator with a contact opening of at least 3 mm VDE 0700 T1 7 12 2 EN 60335 1 must be provided The main switch and or isolator can be secured against unauthorized switching with a U lock If...

Page 46: ...i WW Ger tetypen Twater Frostschutzf hler WW Heizregister R cklauf nur bei WW Ger tetypen Ext 3 Kanalf hler Lieferumfang L ftungsger t Panel Komfortbedienelement mit integriertem Temperaturf hler inkl...

Page 47: ...mperature limiters the STL auto reset trigger temperature 50 C and manual reset trigger temperature 120 C are connected in series Once a safety temperature limiter is triggered the preheater will be d...

Page 48: ...r auxiliary heater battery only Type KWL EC D Pro It is possible to integrate an external hot water aux heater on unit types KWL EC 700 1400 2000 D PRO internal thread IG The heater battery can be reg...

Page 49: ...en closed to put the KWL into ventilation mode 3 2 10 Fire mode fire contact The KWL unit can be put into two operating modes extract air mode or standby mode through the Fire mode func tion Fire cont...

Page 50: ...ight cooling With regard to night cooling the effect of cool outside temperatures is used in comparison to room or inside temperatures The bypass can also be used in transition periods spring and autu...

Page 51: ...riod of time The maximum achievable flow rate and the corresponding static pressure in the ductwork is shown as a result of the ventilator calibration The calibration can be activated on the controlle...

Page 52: ...ions 4 0 Surface mounted controller with touch screen The central ventilation unit is controlled with a surface mounted controller Fig 11 It enables freely definable operating levels within the total...

Page 53: ...the arrow keys to enter the desired time intervals Up to four time intervals can be programmed for each day of the week Example Time interval 1 Time interval 2 Time interval 3 Time interval 4 5 The fo...

Page 54: ...ing RETURN Weekly menu Copy function Transfer copy to week day Example Programming a daily programme 1 Press the On key Daily programme is active 2 Press the Day key to activate the daily menu 3 Press...

Page 55: ...upply air sensor with the arrow keys 3 Return to the main menu by pressing the RETURN key Main menu Temperature value 8 Brightness contrast tone 1 Press the Brightness Contrast key in the main menu 2...

Page 56: ...it therefore increases or decreases the flow rate capacity before reaching the limit value depending on the target limit value comparison Pressing the A symbol again switches the unit back to the manu...

Page 57: ...vice menu PIN Service menu 4 Start mode 1 Select the Start mode function in the service menu confirm by pressing OK 2 Press the ventilator key and set the desired flow rate 3 Set the minutes 2 60 with...

Page 58: ...ld to return to the service menu Service menu Function test display Function test Service menu 10 External sensor 1 Select the External sensor function in the service menu confirm by pressing OK The f...

Page 59: ...e menu 14 Fire mode 1 Select the Fire mode function in the service menu confirm by pressing OK 2 Select the Unit off key the unit switches off in case of fire 3 Select the Extract air key the extract...

Page 60: ...KWL EC D Pro WW Installation and Operating Instructions Add service function symbol explanati on 1 Flow rate Extract air fan 2 Flow rate Supply air fan 3 Supply air outside air temperature Ext 1 4 Pre...

Page 61: ...CHAPTER 5 DIMENSIONS CHARACTERISTIC CURVES EN a A J m n n m F E E B I b z y x Z Y X h H K k Ansicht Revisionsseite unten d c C D B b A a H h J I K k c KWL EC 700 D 957 840 1418 1400 359 350 900 872 3...

Page 62: ...maintenance and installation work or before opening the switch room Danger of electric shock moving parts fan and hot surfaces 6 1 Removing cleaning cross counter flow heat exchanger m DANGER OF INJU...

Page 63: ...rom the nozzle to the fins m Max water temperature 60 C m Do not bend the fins m Clean both sides of the heat exchanger m Allow heat exchanger to dry before installation 6 2 Filter change The inspecti...

Page 64: ...e exchanged for hygiene reasons after one year of operation at the latest If the filters are damp or mouldy they must be exchanged immediately Replacement air filters are also available online at www...

Page 65: ...6 6 Accessories WHSH HE 24V 0 10V Ref no 8318 Temperature control system for hot water heater battery KWL S 700 D Ref no 4206 Symmetrical adapter piece KWL S 1400 D Ref no 4207 Symmetrical adapter pi...

Page 66: ...DE 0700 T1 7 12 2 L1 N PE 2 15V GND1 CO2 24V 0 10V 5 Au enluft Verschlussklappe 230V externe Komponente N open auf 230V 230V N open auf 230V 230V 19 40 41 42 43 44 45 47 N 230V 48 49 Kondensat Schwimm...

Page 67: ...Signal potentialfreier Kontakt 50 51 Externes Signal potentialfreier Kontakt 52 53 max 50m 4 11 Klemmleiste Platine Platine 250V 2A AC1 UX1 GND2 GND2 WW Type 3 20 GND 0 10V 21 oder KWL EC CO Art Nr 99...

Page 68: ...eier Kontakt 52 53 max 50m 4 11 Klemmleiste Platine Platine 250V 2A AC1 UX1 GND2 GND2 WW Type 3 20 GND 0 10V 21 oder KWL EC CO Art Nr 9988 2 KWL EC FF Art Nr 9989 KWL CO Art Nr 4272 KWL FTF Art Nr 427...

Page 69: ...31 Central ventilation units KWL EC D Pro WW Installation and Operating Instructions EN 7 3 Wiring plan KWL EC 700 D Fig 34...

Page 70: ...T 2 T EXT 3 T INT 1 T INT 2 T WATTER T ALARM BU GN WH OG RD PK BN Farbcode nach IEC 757 BK sw schwarz black BN br braun brown RD rt rot red OG or orange orange YE ge gelb yellow GN gn gr n green BU bl...

Page 71: ...3 T INT 1 T INT 2 T WATTER T ALARM BU GN WH OG RD PK BN Farbcode nach IEC 757 BK sw schwarz black BN br braun brown RD rt rot red OG or orange orange YE ge gelb yellow GN gn gr n green BU bl blau blue...

Page 72: ...l Cedex CH HELIOS Ventilatoren AG Tannstrasse 4 8112 Otelfingen GB HELIOS Ventilation Systems Ltd 5 Crown Gate Wyncolls Road Severalls Industrial Park A HELIOS Ventilatoren Postfach 854 Siemensstra e...

Reviews: