The maximum fan speed setting can be selcted to be active eiher with adjustments
(CO
2
sensor and humidity sensor). The selection is done with the + and - buttons.
The language (German, English, Francais) is selected with the + and - buttons.
The general factory settings can be restored by pressing the + and - buttons
simultaneously.
The adjustment interval for humidity and CO
2
sensor adjustments is selected
with the + and buttons. The adjustment intervall refers to minutes.
The maintenance reminder is acknowledged by pressing the + and
buttons simultaneously.
The contrast setting for the control panel display is changed with the
+ and buttons.
The address of the control panel is changed with the + and - buttons. Two control
panels cannot have the same address. If control panels have the same address, they
will go to the bus fault state and will not operate.
1.3.6. Mode of operation of the maximum speed setting
1.3.7. Choosing the language version
1.3.8. Restoring the factory settings
1.3.9. Adjustment interval
1.3.10. Acknowledging the maintenance reminder
1.3.11. Contrast of the control panel display
1.3.12. Adress of the control panel
Max Speed limit
with adjustment
Kieli / Language
English
Factory settings
see manual
Adjust interval
10
Mainten. reset
Press + and -
Display contrast
05
Panel adress
1
The desired cell bypass temperature is selected with the + and buttons. If outdoor
temperature is lower than cell bypass temperature, the summer/winter damper is in the
winter position.
1.3.15. Changing the operating temperature of heat recovery cell bypass
Cell bypass
10C
The desired adjustment value for the DC fan is selected with the + and buttons. The
rotation speed of the supply air fan can be lowered by decreasing the percentage
value.
1.3.14. Adjusting the DC fan of the supply air side
DC fan - supply
100%
1.3.13. Adjusting the DC fan on the extract air side
DC fan exhaust
100%
The desired adjustment value for the DC fan is seleced with the + and buttons. The
rotation speed of the extract air fan can be lowerd by decreasing the percentage value.
In order to enter into the menu "change clock time", pr and - buttons
simultaneously.
Move cursor with arrow keys und change the values with + and - buttons.
To complete the changes quit over "exit".
monday (day=1), hour 15 (hour=15), minutes (min=30).
NOTE: After a power failure the clock time persisted!
1.3.5. Change clock time
Change clock time
Press + and -
day hour Min
1
15
30 Exit
day
day 1-7
1=monday, 2=thursday etc.
hour
hour 0 - 23
min
minutes 0 - 60
exit
accept settings and quit.
OPERATION INSTRUCTION OF THE CONTROL PANEL