The preheating temperature for the defrost function of the heat recovery cell is chosen
with + and buttons.
1.3.24 Preheating temperature for the defrost function of the heat recovery cell
Preheater
07C
The stopping temperature of the supply air fan for the defrost function of the heat
recovery cell is chosen with the + and - buttons.
1.3.23 The stopping temperature of the supply air fan for the defrost function of the heat recovery cell
Input fan stop
05C
The hysteresis of the defrost function of the heat recovery cell is selected
with the + and buttons.
1.3.22 The hysteresis of the defrost function of the heat recovery cell
Hysteresis
03C
The intervall for the maintenance reminder is selected with the + and -
buttons. The maintenance reminder interval refers to months.
1.3.21 Choosing the interval for the maintenance reminder
Maintenance rem.
04
Without function!
1.3.20 Choosing post-heating for the unit
Radiator type
electric rad.
Automatic or manual search of the basic humidity level.
The selection istdone with the + and - buttons.
1.3.19 Choosing the basic humidity level
RH-level setting
automatic
The desired setpoint is selected with the + and - buttons, unless automatic search of the
basic humidity level is used.
1.3.16. Setpoint of the basic humidity level
Basic %RH level
40%
The mode of operation of the switch (either fireplace or booster switch) is selected with the
+ and - buttons.
NOTE!
Fire and building regulations must be observed. (See page 4).
1.3.17. Mode of operation of the fireplace/booster switch
Switch type
Fireplace switch
Without function!
Cascade adjust
Off
1.3.18 Choosing cascade control for supply air temperature
The desired maximum fan speed is selected with the + and buttons. Maximum fan
speed is on either with adjustments or permanently. See Section 1.3.6., Mode of
operation of the maximum speed setting.
1.3.26 Choosing maximum fan speed
MAX fan speed
8
The setpoint for CO
2
-adjustment is chosen with + and - buttons.
1.3.25 Changing the setpoint for carbon dioxide adjustment
CO2-setting
0900 PPM
16
OPERATION INSTRUCTION OF THE CONTROL PANEL