7.3 Menu structure
100 Pa
Δ
p
Display after turning on the voltage supply.
Switch over between actual value display and
“
INFO
”
with
the key shortcut for Escape (Esc =
▼
+
▲
).
INFO
Selection of the menu group (e.g. BASE SETUP) to the right through the
▼
-key, to the
left through the
▲
-key.
Youcangotothemenuitemsinthe
menu
groups (e.g. mode) by using the P key. Use the
arrow keys to move up and down within the menu group.
To make adjustments, press the
P
key after selecting the menu item. If the previously set
value starts to
fl
ash, it can be adjusted with the
▼
+
▲
keys and then saved with the
P
key. To exit the menu without making any changes, use the
“
Esc
”
short-key, i.e., the
originally set values remain.
Example for Mode
2.01
(Factory setting)
INFO
▼
▲
SETTING
▼
▲
BASE SETUP
P
↓
↑
Esc
P
↓
↑
Esc
P
↓
↑
Esc
100 Pa
Δ
p
500 Pa
Setpoint 1
4.01
Mode
▲
▼
▲
▼
▲
▼
500 Pa
Setpoint 1
500 Pa
Setpoint 2
1: metric
Units
▲
▼
▲
▼
▲
▼
Reprogramming Mode
4.01
to
4.00
in
“
BASE SETUP
”
1
2
3
4
5
6
7
4.01
Mode
P
«
4.01
»
Mode
▲
«
4.00
»
Mode
P
4.00
Mode
7.4 Display unit (metric / inch)
The display can be switched between SI units (factory setting) and imperial (US) units
see BASE SETUP / Units.
Conversion factor Pressure: 1,0 in.wg = 254 Pa
Installation and Operating Speci
fi
cation
EDR
Programming
L-BAL-E292-GB 1841 Index 001
Part.-No.
9/15