7 Programming
7.1 Select operation mode
Information
Simple installation is possible through the selection of the preprogrammed mode of
operation.
This determines the basic function of the device, factory set
4.01
.
Mode
Function
4.00
Pressure sensor: output 0...10 V proportional to measuring range
4.01
Pressure controller (PID): output 0...10 V depending on adjusted Setpoint and meas-
ured actual value.
7.2 Start-up
Procedure
1. You must mount and connect the device in accordance with the operating instruc-
tions.
2. Double check that all connections are correct.
3. The supply voltage must match the information on the rating plate.
4. Set the mode, unit and measuring range and adjust the sensor in the
BASE
SETUP
.
5. Set the parameters for control operation for the mode
4.01
under
SETTING
.
Information
When saving the Operating Mode, the factory settings are stored. Therefore all the
settings you have made, are lost.
Installation and Operating Speci
fi
cation
EDR
Programming
L-BAL-E292-GB 1841 Index 001
Part.-No.
8/15