14 Parameter Description
84
KRONOS 20
No. Name
Signification
3430 GasTotalDeltaPress
Level:
1
Range:
0..30000 Pa
Page(s):
Calculated overall pressure difference
3431 GasValveOpeningArea
Level:
1
Range:
0..65535 mm²
Page(s):
Calculated opening area of the E-LES
3440 ZPRDroopPressure
Level:
1
Range:
0..30000 Pa
Page(s):
Calculated pressure droop of the zero pressure regulator
3450 GasDensity
Level:
1
Range:
0,5..3 kg/m³
Page(s):
Current gas density (variation only at CH4 content
feedback)
3451 CalorificValue
Level:
1
Range:
5..100 MJ/m³
Page(s):
Current gas calorific value (variation only at CH4 con-
tent feedback)
3452 LambdaStoichiometric
Level:
1
Range:
1..30 m³/m³
Page(s):
Current gas lambda stoichiometric (variation only at
CH4 content feedback)
3453 GasFlowRateDesired
Level:
1
Range:
0..2500 m³n/h
Page(s):
Calculated gasflow setpoint based on lambda setpoint
(3462
LambdaDesiredValue
)
3454 GasFlowRateActual
Level:
1
Range:
0..2500 m³n/h
Page(s):
Calculated gasflow rate based on output power feed-
back (2914
MeasuredPower
)
3460 LambdaTempCorr
Level:
1
Range:
-1,25..1,25
Page(s):
Current factor for temperature dependant lambda cor-
rection
3461 LambdaMap
Level:
1
Range:
0..2,5
Page(s):
Current value from lambda map
3462 LambdaDesiredValue
Level:
1
Range:
0..2,5
Page(s):
Temperature corrected actual lambda setpoint from
lambda map
Summary of Contents for E-LES 30
Page 2: ......
Page 8: ......
Page 104: ...17 Order Form for KRONOS Systems 96 KRONOS 20 17 Order Form for KRONOS Systems...