Type
Code
Description
Solution
Unit working
statue
Blinking
times
Compressor stops
S08 Defrosting Failure
Compressor stops
and AH (or HBH)
works
S09
Water outlet Temp.
too low protection
in heating/hot water
Compressor stops and AH (or HBH) starts if water outlet temperature
is lower than 15
℃
in heating and hot water mode. Compressor
restarts when this temperature is higher than 17
℃
. This is a
protection for protecting the safety of the compressor, as too low
water temperature in heating or hot water mode may kill the
compressor.
Compressor stops
S07
Water outlet Temp.
too high protection
in heating/hot water
Compressor stops if water outlet is higher than 57
℃
in heating or hot
water mode. Check whether temperature sensor Tc and Tw is OK and
well connected; whether set water temperature too high; whether
system flow rate too small.
Unit stops
S05
Serial port connect
error
Communication failure between operation panel and the indoor or
outdoor PCB. Check the cable connection in between. Check whether
the last three switches on outdoor power PCB are set to 001; Whether
four switches on indoor PCB are set to 1000. Unit recovers when
communication recovers.
Compressor stops
S06
Water outlet Temp.
too low protection
in cooling
Compressor stops if water outlet is lower than 5
℃
in cooling mode.
Check whether temperature sensor Tc is OK and well connected;
whether set water temperature too low; whether system flow rate too
small.
Protection
Unit stops
S04
Communication
failure
Communication data lost too much. Check whether communication
cable is longer than 30M; whether there has a source of the
disturbance nearby the unit. Unit recovers when communication
recovers.
If unit continuously failed to finish the defrosting operation for three
times, it stops and gives failure code S08. This can only be recovered
by re-powering the machine. Please check whether the actual water
temperature is too low for the unit to defrost, so the plate heat exchanger
has the risk of freezing up.
Compressor stops
S10
Too small water flow
rate failure
If unit stops due to “too small water flow rate”protection code(S02)
over three times in certain period of time, unit stops and gives S10
failure code. It can only be recovered by re-powering the unit. Check
the water system, especially the filter, check the working statue of
water pump.
Compressor stops
S11
Indoor Anti-freezing
Protection Failure in
Cooling
If unit stops due to “Indoor Anti-freezing protection in cooling (S01)”
over three times in certain period of time, unit stops and gives S11
failure code. It can only be recovered by re-powering the unit.
E01
System
failure
Communication
between operation
panel and indoor
PCB or outdoor
PCB failure
Communication failure between operation panel and the indoor or
outdoor PCB. Check the cable connection in between. Check whether
the last three switches on outdoor power PCB are set to 001; Whether
four switches on indoor PCB are set to 1000. Unit recovers when
communication recovers.
E02
Communication
between outdoor
main control PCB
and module PCB
Check the communication cable between outdoor power PCB and
deiver PCB. Check whether outdoor power PCB and deiver PCB is
broken.
E03
Compressor phase
current failure
(open/short circuit)
Check whether the power cable to compressor is broken or short-
circuit.
E04
Compressor phase
current overload
(over current)
Check whether the power cable to compressor is broken or short-
circuit.
E05
Compressor driver
failure
Check whether compressor drive PCB is broken, or cable to
compressor is wrong connected.
E06
Module VDC over
high/low voltage
failure
Input voltage too high or too low.
E07 AC current failure
Check the current to outdoor unit, and compare it with the unit
current shown on the operation panel. If the difference is not big,
check whether the system has enough refrigerant (more likely it is not
enough refrigerant that caused this abnormal low current). If the
difference is big, outdoor power PCB is broken. Please replace it with
a new one.
E08 EEPROM failure
Cut the unit power and short-circuit JP404 port on outdoor power
PCB, repower the unit, cut power again and cancel the short-circuit
on JP404 port. If still not OK, replace the outdoor power PCB.
Compressor stops
Compressor stops
Compressor stops
Compressor stops
Compressor stops
33
34
35
36
37
Compressor stops
38
39
Compressor stops
40
Compressor stops
98
9. Failure Code