5. Installation Walkthrough
5.4. Outdoor Unit Installation
【
】
A. On a concrete stand
【
】
B. On brackets on the wall
The
piping and signal cable between indoor and
outdoor unit should go through the wall by using a
wall sleeve.
water
The hole should lean to outside a little bit(
≥
8 degrees),
to avoid rain water or condensate water flow back to
the indoor.
Please add rubber absorber under the outdoor unit, to reduce the vibration.
Weather
shielter
Wall sleeve
1.The unit must be located on a flat,solid,preferably cemented surface.
2.When installing the unit,introduce a tilt of 1cm/m for rain water evacuation.
3.When installing the unit in harsh climatic conditions,sub-zero temperature ,snow,humidity..,
it is recommended to raise the unit off the ground by about 50cm.
4.It is recommended to have a base with following size for these units:
5.Rubber vibration absorbing mountings are recommended.
6.When sitting he unit,take care to leave sufficient
free space all around it for carrying out
maintenance.
≥
50cm
A:If needs to hang the outdoor unit on the wall, please do as followings:
1.Adjust the location of the wall
according to the distance between two feet of the unit.
2.Fix the
on the wall with expansion bolts.
3.Place the outdoor unit on the
.A
4.Fix the unit to the bracket.
brackets
brackets
brackets
Vibration absorbers are recommended to reduce
vibration and noise.
Bolt
Vibration absorber
Nut
Gasket
1
2
3
4