Functions and control
17
Domestic air conditioner
After outdoor unit is off, the EEV opening keep the current on for 5 s, then open the EEV completely for
2 minutes, then become 120 steps (cooling) or 60 steps (heating).
The EEV opening will increase if SH (superheat degree) >0 while decrease if SH<0.
Adjust frequency:
If |SH|=0, 60s/ 1 step
If |SH|
≥
3,and
△
SH=0, 10s/ 1 step.
If 3
≥
|SH|
≥
0, 30s/ 1 step.
△
SH= current SH- last SH
SH= Ts (suction temp)-Tc1 (indoor coil temp)-Tsh (fixed data, depend on different models, -1~2)
7.1.4 Four way control
For the details of defrosting four-way valve control, see the defrosting process.
Four way working in other ways:
Under the mode of heating, open the four-way valve, when the compressor is not started or changed to
non-heating mode, make sure the compressor is stoped for 2 minutes, and then close the four-way valve.
7.1.5 Protection function
7.1.5.1 TTC high temperature-preventing protection
Once the machine is started, it can run TTC(air-blowing temp)
overheating protection of air-blowing,
but air-blowing sensor malfunction must alarm after 4 minutes during which the compressor is started
(during the course of self-detection, there’s no such limitation)
Sensor detection methods: 100 times (one cycle of procedure run is one time, and about 5ms,
detection method for eac
●
h time: continuously sampling for 8 times, then order them and take the mean
value of the middle
●
2 values), take the mean value.
TTC
(℃)
09K
(
●
12K
)
Abnormal stop
110
(
110
)
Decreasing the frequency rapidly
(
1HZ/second
)
107(106)
Decreasing the frequency slowly (1HZ/10seconds)
105(104)
The frequency doesn’t change.
102(102)
Increasing the frequency (1HZ/10second)
95(93)
Increasing the frequency
(
1HZ/1second
)
TTC>=110
℃
●
lasts for 20 seconds. Overheating protection of air-blowing, alarm malfunction to the
indoor, others don’t last.
●
7.1.5.2 TC high temperature-preventing control of the indoor heating unit
:
Tpg_indoor is the highest value of the effective indoor unit (start it and it is in accord with the running
Summary of Contents for JZ050-C1
Page 11: ...Pinping diagrams 9 Domestic air conditioner 4 Pinping diagrams EEV EEV...
Page 12: ...Operation range 10 Domestic air conditioner 5 Operation range 10 0 21 27 35 20 40 60 43 20 40...
Page 15: ...Wiring diagrams 13 Domestic air conditioner Wiring diagrams...
Page 57: ...Circuit diagrams 55 Domestic air conditioner 13 2Module board circuit diagram...
Page 58: ...Sincere Forever...
Page 59: ...Wall Mounted Type DC Inverter FREE MATCH NEW1 5P Series SERIES JZ050 C1...