Amax Bmax
C
D
E
21
10
20
5
5
7
20
1.
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
A
B
Outdoor unit
Indoor unit
Oil trap
To bend a pipe, give the roundness as large as possible not to crush the pipe ,
and the bending radius should be 30 to 40 mm or longer.
Connecting the pipe of gas side rst makes working easier.
The connection pipe is specialized for R32.
Half union
Flare nut
Torque wrench
CAUTION
Be careful that matters, such as wastes of sands,water,, etc. shall not enter the pipe.
The standard pipe length is Cm. If it is over D m, the function of the unit will be affected. If the pipe has
to be lengthened, the refrigerant should be charged, according to E g/m. But the charge of refrigerant
must be conducted by professional air conditioner engineer. Before adding additional refrigerant,
perform air purging from the refrigerant pipes and indoor unit using a vacuum pump,then
Spanner
Forced fastening without careful centering may
damage the threads and cause a leakage of gas.
Pipe Diameter( )
Fastening torque
Liquid side6.35mm(1/4")
Liquid/Gas side9.52mm(3/8")
Gas side 12.7mm(1/2")
Gas side 15.88mm(5/8")
Max.Elevation:
In case the elevation A is more
than 5m, oil trap shoud be
installed every 5~7
Max. Length:
In case the pipe length B is
more thanDm, the refrigerant
should be charged, according
to E g/m.
Connection of pipes
charge
additional refrigerant.
Amax
Bmax
2.
M i n. Length: B min
20
Bmin
3
3
5
15
JZ070-C1
JZ070-C1
JZ035-A1
M2T050-D1
JZ050-A1
JZ035-A1
JZ050-A1
In case the elevation B is more than 5m,
oil trap shoud be installed every 5~7m
Max. Length: B1 max =20m B2 max =20m
Max.Elevation: A1 max =15m A2 max =15m
In case the pipe total length (B1+B2) is more than
20m, the refrigerant should be charged, according
to 20 g/m.
B
Outdoor unit
Indoor unit
A1
B1
Indoor unit
A2
B2
Outdoor unit
Indoor unit
B1
Indoor unit
B2
Outdoor unit
Indoor unit
Oil trap
A3
A3 max =15m
(B1+B2) max =30m
Outdoor unit
Indoor unit
A1
B1
Indoor unit
A2
B2
CAUTION
Indoor unit
Min. Length: B1 min =3m B2 min =3m
M2T050-D1
JZ025-C2
JZ035-C2
JZ050-C2
JZ025-A1
18 20N.m
30 35N.m
35 45N.m
45 55N.m
JZ025-C2
JZ035-C2
JZ050-C2
JZ025-A1
Summary of Contents for JZ025-A1
Page 2: ......
Page 42: ...WARNING CAUTION N Open the window and well ventilated the room explosion proof fuse 13...
Page 44: ...R32 2 3 R 2 3 R R32 R32 R32 R32 R32 15...
Page 46: ...R32 R32 R32 R32 R32 R32 R32 R32 R32 17...
Page 47: ...3 R32 R32 R32 R32 R32 R32 R32 18...
Page 48: ...R32 R32 R32 R32 R32 R32 R32 R32 10A HFC 410A 19...
Page 51: ...22...
Page 52: ...23 R32 R32...