Gas fired igniter ZT0
Installation and initial commissioning
- 32 -
Status: 11-2018
6.3
Electrical function test
This test must only be carried out by a specialist trained in the
handling of the plant and its components.
Additionally required protective gear:
Face protection
Safety gloves
Required special tools:
Test diode A10Z2 (accessory part)
DANGER!
Fatal danger due to electrical voltage or high
voltage!
High voltage is present in the ignition electrode for
ignition purposes. Due to the supply voltage of the
ionisation flame monitor, electrical voltage is also
applied to the flame rod. Contact with the
electrodes could be fatal.
– Never come into contact with the ignition
electrode or the flame rod.
DANGER!
Escaping fuel or the release of other devices
may cause an explosion!
A release of the gas fired igniter can cause the
start of subsequent devices (burners).
– Any other devices such as burners and valves
shall therefore be blocked.
DANGER!
Risk of explosion due to leaking gas!
Accidental gas leaks can cause an explosion or
serious burns!
– Before testing, shut off the gas valve!
– Ensure that no residual gas remains, if
necessary inert the gas lines.