Indirect Fired Construction Heater

Operating Instructions and Owner’s Manual

3

IMPORTANT

Before using the heater, read and understand all instructions and 
follow them carefully. The manufacturer is not responsible for 
damages to goods or persons due to improper use of units.

GENERAL RECOMMENDATIONS

This indirect-fired heater runs on natural gas or L.P.G. and is fitted 
with a flue to take the fumes away through the chimney.
Prior to shipping, the heater is configured for either natural gas 
or LP, labeled on the gas selector valve for the correct fuel type 
and given a complete functional test. To change the type of gas, 

follow the detailed instructions indicated in section “CHANGING 
TYPE OF GAS”.

 Always follow local ordinances and codes when using this 
heater:

•Read and follow this owner’s manual before using the heater.
•Use only in places free of flammable vapors or dust content.
• Never use heater in immediate proximity of flammable 

materials (the minimum distance must be 6 ft.).

•Make sure fire fighting equipment is readily available.
• Make sure sufficient fresh outside air is provided according to 

the heater requirements. Direct combustion heaters should 
only be used in well vented areas in order to avoid carbon 
monoxide poisoning.

• The heater is installed near a chimney to take away the fumes 

(see “Ventilation” on page 5) and connected to an electrical 

switchboard.

• When the heater is connected to a flue pipe, the flue pipe 

shall terminate in a vertical section at least 3 feet long and 

sufficient draft shall be created to assure safe and proper 
operation of the heater.

• Never block air inlet (rear) or air outlet (front).
• In case of very low temperatures add kerosene to the heating 

oil.

• Make sure heater is always under surveillance and keep 

children and animals away from it;

• Before starting the heater always check free rotation of 

ventilator fan.

• Indirect fired units only can be connected to air ducts to 

distribute warm air, with respect to the max. static pressure 

declared (see “TECHNICAL SPECIFICATION” sheet).

•Unplug heater when not in use.

TECHNICAL SPECIFICATIONS

HS 4000IDG

Heat input

[kBTU/h]

380

Air flow

[cfm]

3,250

Heat output

[kBTU/h]

328.7

Natural Gas

Supply pressure

[in WC]

min 7’ w.c.

max 10” w.c.

Burner pressure

[in WC]

6.40

Fuel consumption

[CFH]

355.97

Position of gas 
selector value

LPG

Supply pressure

[in WC]

min 8’ w.c.

max 13’ w.c.

Burner pressure

[in WC]

7

Fuel consumption

[CFH]

133.89

Position of gas 
selector value

Power 
supply

Phase

1

Voltage

[V]

120

[Hz]

Frequency

60

Electric consumption

[W]

1400

[A]

13.0

Adjustment of combustion air 

fl

ap

[N]

3.0

Ring Nozzle

[in]

N. 12 holes x

0.106”

Gas inlet connection thread

[psi]

3/4” HPT

Flue

[in]

5.91

Static pressure

[in]

0.60

Compulsory 

fl

ue draft

[in]

0.05

Maximum air temperature

[°F]

250

Base unit

Dimensions, L x W x H

[in]

72.3 x 31.6 x 

30.4

Weight

[lb]

306

Packaging

Dimensions, L x W x H

[in]

74.1 x 26.0 x 

35.83

Weight

[lb]

361

TABLE 1

Summary of Contents for 4000IDG-HD

Page 1: ...D OWNER S MANUAL INDIRECT FIRED PORTABLE HEATER This is a vented portable heater It uses air oxygen from the area in which it is used Adequate combustion air and ventilation must be provided Refer to...

Page 2: ...INSTRUCTIONS 6 MAINTENANCE 7 VENTILATION 7 TROUBLE SHOOTING 8 WIRING DIAGRAMS 9 PARTS DIAGRAM LIST 1 1 13 WARRANTY 14 WARNING READ THE INSTRUCTIONS GIVEN IN THIS MANUAL BEFORE USING THE APPLIANCE DO N...

Page 3: ...onnected to an electrical switchboard When the heater is connected to a flue pipe the flue pipe shall terminate in a vertical section at least 3 feet long and sufficient draft shall be created to assu...

Page 4: ...TION ELECTRODE 7 COOLING FAN 8 9 10 11 12 13 14 8 PHASE NEUTRAL LINE TEST PUSH BUTTON 9 RESET BUTTON HOLD FOR 3 SEC 10 HEATING SWITCH 1 1 ROOM THERMOSTAT PLUG 12 VENTILATION MODE SWITCH 13 POWER LED 1...

Page 5: ...fied Petroleum Gases ANSI NFPA 58 and CSA B149 1 Natural Gas and Propane Installation Code WARNING Never use free flames to detect gas leaks The following operations must now be carried out Plug in th...

Page 6: ...scribed in Tab I and by following instruction After having moved the handle into the opposite position put again the fixing screw and a new sticker on it stating the gas which has to be used a number...

Page 7: ...ent of H T connectors to the electrodes and check H T cables remove burner assembly clean and check electrode settings adjust according to scheme GAP OF ELECTRODES Flue Connections Diagram VENTILATION...

Page 8: ...V transformer Flame control box defective Replace control box Photocell defective Clean or replace photocell Not enough or no fuel at all at burner Check state of motor pump plastic coupling Check fue...

Page 9: ...OLENOID VALVE 1 AP CONTROL BOX EV2 SOLENOID VALVE 2 FA FAN THERMOSTAT FO PHOTOCELL CN CONNECTOR CO CONDENSER RF HEATER FILTER MV FAN MOTOR LI2 OVERHEAT SAFETY ST ELECTRIC PILOT PE GROUND DRAWING LEGEN...

Page 10: ...al 57 58 59 62 45 46 47 49 53 23 60 01 02 04 26 05 10 09 12 A 28 22 B 21 06 37 27 28 03 25 42 43 36 41 82 85 84 83 80 24 38 56 17 18 35 C 30 29 40 39 11 20 16 19 32 Optional 08 07 100 101 78 68 67 66...

Page 11: ...E10324 FUSE 25A 49 N A E20319 Ground terminal board 50 50731 E20305 Terminal Board 12 pin 51 E10938 H T Transformer 52 E40234 Flame Control Box REF P N ALT DESCRIPTION 53 G06073 Support Plate 56 5032...

Page 12: ...Instructions and Owner s Manual 12 HS4000 IDG ENERCO GROUP INC Indirect Fired Portable Heater 12 Operating Instructions and Owner s Manual 147 126 126 127 130 131 129 132 128 103 130 131 134 138 143...

Page 13: ...Wheel Locking Pin 138 40524 G06422 Reinforcement Plate 139 G06461 9005 Support 140 40527 G06425 9005 Panel 141 40526 G06424 9005 40526 142 40525 G06423 9005 Handle 143 40505 C10203 Handle 144 40535 M...

Page 14: ...purchase date and the name and address of the dealer from whom you purchased our product The foregoing is the full extent of the responsibility of the Company There are no other warranties express or...

Page 15: ...sez quiconque n ayant pas lu les pr sentes instructions d assembler d allumer d ajuster ou de faire fonctionner cette fournaise INSTRUCTIONS D UTILISATION ET MANUEL DU PROPRI TAIRE APPAREIL DE CHAUFFA...

Page 16: ...T R SIDUEL DOIT TRE FOURNI SUR LE PANNEAU DE DISTRIBUTION PRINCIPAL D BRANCHEZ LA FOURNAISE AVANT D ESSAYER TOUT ENTRETIEN OU R PARATION V RIFIEZ TOUJOURS LE C BLE D ALIMENTATION AVANT L UTILISATION I...

Page 17: ...fum e ce dernier doit se terminer en une section verticale d une longueur d au moins 61 cm 2 pi et un courant d air suf fisant doit tre cr pour garantir un fonctionnement s curitaire et ad quat de l a...

Page 18: ...UMAGE 7 VENTILATEUR DE REFROIDISSEMENT 8 9 10 11 12 13 14 8 BOUTON POUSSOIR DE TEST DE LIGNE PHASE NEUTRE 9 BOUTON DE R INITIALISATION 10 INTERRUPTEUR DE CHAUFFAGE 1 1 PRISE DE THERMOSTAT DE LA PI CE...

Page 19: ...e la manipulation des gaz liqu fi s et au Code national CSA B149 1 d installation du gaz naturel et du propane AVERTISSEMENT Ne jamais utiliser des flammes nues pour d tecter les fuites de gaz Les op...

Page 20: ...le type de gaz utilis plusieurs diff rents autocollants sont fournis avec l appareil AVERTISSEMENT La pression du br leur ne doit pas tre ajust e l appareil de chauffage est pr t recevoir le nouveau t...

Page 21: ...rim v rifiez le bon raccord des connecteurs de haute tension aux lectrodes et v rifiez les c bles de haute tension Retirez l as semblage du br leur nettoyez et v rifiez les r glages de l lectrode r gl...

Page 22: ...use Remplacez la bo te de contr le Cellule photo lectrique d fectueuse Nettoyez ou remplacez la cellule photo lectrique Manque ou aucun carburant au niveau du br leur V rifiez l tat du couplage plasti...

Page 23: ...n 16 ou 18 ou l quivalent tel que pr cis aux pr sentes MOD LE S RIE 4000IDG FU FUSIBLE RV TEMP IT TRANSFORMATEUR DE HAUTE TENSION TA THERMOSTAT POUR LA PI CE LV1 THERMOSTAT DE SURCHAUFFE RE RELAIS EV1...

Page 24: ...Portable Heater 11 Operating Instructions and Owner s Manual 57 58 59 62 45 46 47 49 53 23 60 01 02 04 26 05 10 09 12 A 28 22 B 21 06 37 27 28 03 25 42 43 36 41 82 85 84 83 80 24 38 56 17 18 35 C 30 2...

Page 25: ...50093 E20508 PORTE FUSIBLE 47 40508 E10324 FUSIBLE 25 A 49 N A E20319 Panneau de borne de terre 50 50731 E20305 Borne panneau 12 broches 51 E10938 Transformateur HT 52 E40234 Bo tier de commande de f...

Page 26: ...alimentation indirecte pour construction Instructions d utilisation et manuel du propri taire HS4000 IDG ENERCO GROUP INC Indirect Fired Portable Heater 12 Operating Instructions and Owner s Manual 14...

Page 27: ...ondelle 137 40534 M20505 Goupille de blocage de la roue 138 40524 G06422 Plaque de renfort 139 G06461 9005 Support 140 40527 G06425 9005 Panneau 141 40526 G06424 9005 40526 142 40525 G06423 9005 Poign...

Page 28: ...les d tails concernant la r clamation De plus indiquez la date d achat et le nom et l adresse du fournisseur duquel vous avez achet notre produit Ce qui pr c de est la pleine tendue de la responsabili...

Reviews: