NOVUS TOP DV GAS APPLIANCE INSTALLATION INSTRUCTIONS

Note:

 

Squeezing the pipe slightly to fit may be

necessary.

Note:  

Make sure that the seams are NOT

aligned in order to prevent unintentional

disconnection.

Figure 20

Figure 21

Figure 22

3. ASSEMBLING  THE  VENT  SECTIONS

a. Attaching the Venting to the Appliance

To attach the first VP section to the appliance collars, slide the

flared end of the inner flue of the VP section over the inner collar

on the appliance. At the same time, insert the outer flue into the

outer  collar  on  the  appliance.  Push  the  vent  section  into  the

appliance  collar  until  all  the  lances  have  snapped  into  place.

Tug  slightly  on  the  vent  to  confirm  it  has  completely  locked  in

place.

b. Assembling Vent Sections

1)

Start the flared inner flue of section “A” over the inner flue of

section “B”.

2)

Insert the outer flue of section “A” into the outer flue of section

“B”. See Figure 20.

Once both inner and outer flues are started, press section

“A” into section “B” firmly until all lances have snapped into

place. Tug slightly on section “A” to confirm it has completely

locked into place. See Figure 21.

c. Assembling Minimum Installation (MI) Sections

MI sections are non-unitized so that they can be cut to a certain

length. To use these sections, they must be cut to length from

the non-expanded end. See Figure 22. They can then be attached

by first connecting the expanded end of the MI inner flue with the

inner flue from the adjacent vent section and securing with three

screws. The expanded portion of the MI inner flue must overlap

completely with the untreated end of the adjacent vent section.

The outer flue can then be inserted into the adjacent outer flue

expanded end and attached to the next vent section with three

screws. The other end of the MI vent section can then be attached

by fitting a snap lock section to it and snapping it together as

normal.

All manuals and user guides at all-guides.com

Summary of Contents for GNDC30

Page 1: ...y phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation a...

Page 2: ...nting must not be connected to chimney flue servicing a solid fuel burning appliance or a gas fuel burning appliance 7 NEVER use gasoline gasoline type lantern fuel kerosene charcoal lighter fluid or...

Page 3: ...atest edition in the U S A and the CAN CGA B149 Installation Codes in Canada This Novus Series gas appliance has been tested and listed for use in manufactured housing mobile homes These installation...

Page 4: ...de Number B Black Firebox GNDC36LEB EXAMPLE Gas NOVUS Direct Vent Heat Circulating 36 Propane Gas Electronic Ignition appliance with Black Firebox Components Description CS Cap Shield VP TV Vertical T...

Page 5: ...gure 2 Appliance Clearances to Combustible Materials A hearth extension is not required for this appliance L E D O M A B C D E 0 3 C D N G 9 2 3 4 4 3 7 8 85 8 3 3 4 3 1 2 3 3 C D N G 2 3 3 4 7 3 7 8...

Page 6: ...3 H D N G 8 7 1 4 4 3 6 3 This appliance may be placed on a smooth combustible or noncombustible continuous flat surface When the appliance is installed directly on carpeting tile or other combustibl...

Page 7: ...as fuel burning appliance WARNING RISK OF FIRE If you have chosen horizontal termination be sure there are no future obstructions from trees bushes snow drifts etc CAUTION Provisions shall be made to...

Page 8: ...n Never allow the vent to run downward This could cause high temperatures and may present a fire hazard Figure 8 Vent Lengths with Two Elbows Figure 9 Vent Lengths with Three Elbows Note Horizontal ru...

Page 9: ...national codes and not be easily blocked or obstructed If the hole being penetrated is of noncombustible materials a 9 diameter hole is acceptable Note Exterior wall thickness must be a minimum of 4 t...

Page 10: ...6 feet 1 8m minimum J Clearance to non mechanical air supply inlet into building or the combustion air inlet to any other appliance 12 inches 30 cm minimum K Clearance to mechanical air supply inlet...

Page 11: ...aterial WARNING The horizontal run of vent must have a rise for every 1 ft of run towards the termination Never allow the vent to run downward This could cause high temperatures and may present a fire...

Page 12: ...ter vent Figure 17 Installing the Firestop Spacer e Chase Termination Installation Figure 18 and 19 and Table 1 specify minimum chimney heights for various pitched roofs These chimney heights are nece...

Page 13: ...into the outer flue of section B See Figure 20 Once both inner and outer flues are started press section A into section B firmly until all lances have snapped into place Tug slightly on section A to...

Page 14: ...utoff valve The incoming gas line should be piped into the valve compartment and connected to the 1 2 FIP connection provided on the manual shutoff valve All connections must be tightened and checked...

Page 15: ...C D N G 0 3 H D N G 0 3 C D N G m m 6 5 2 n i 1 0 1 m m 3 4 2 n i 6 9 0 e z i S e c i f i r O s a G e n a p o r P m m 0 5 1 n i 9 5 0 n m u l o C r e t a W s e h c n i s e t a c i d n i Table 2 Gas In...

Page 16: ...o a thermostat If connecting a 24V thermostat not supplied disconnect the black wire from the transformer at the ignition control Connect the thermostat wires between the ignition control and the blac...

Page 17: ...will withstand high temperatures General Electric RTV103 Black or equivalent Rutland Inc Appliance Mortar 63 or equivalent A high temperature sealant 1 8 inch wide minimum must be used to close off g...

Page 18: ...but does not cover the holes in the burner pan This will provide the glowing embers look See Figure 37 Figure 36 Placing the Vermiculite and Lava Rock top logs removed for clarity Figure 37 Placing th...

Page 19: ...P Read the safety information above on this label 2 Turn wall switch to the OFF position 3 This appliance is equipped with an ignition device which automatically lights the burner Do not try to light...

Page 20: ...ANCE 1 Turn wall switch to the OFF position or set thermostat to lowest setting 2 Open the control access panel 3 Turn manual shutoff valve to CLOSED Wait five minutes to clear out any gas Then smell...

Page 21: ...decide to shut down the appliance for a long period of time a Turn all wall switches to OFF b Turn pilot knob on valve to OFF c Turn the gas line to CLOSED Lighting the Appliance During Regular Use Tu...

Page 22: ...l B 2 o t n i g e b l l i w s e m a l f e h t d n a n o i t a r e p o l a m r o n f o t l u s e r a s i s i h T n r u b o t d e w o l l a s i e c n a i l p p a e h t s a w o l l e y 3 e c n a i l p p...

Page 23: ...re cleaning 2 CHECKING THE FLAME PATTERNS Visually check the flame of the burner periodically making sure the flames are steady not lifting or floating The flame color should be blue with yellow tips...

Page 24: ...THE GLASS See Figure 44 Never operate this appliance without the glass properly secured in place or if the glass if broken or chipped In the event of glass breakage carefully remove the glass frame Th...

Page 25: ...ote Control Standing Pilot RCT MLT HTL Multi Function Remote Control SMART STAT HTL Remote Control with Thermostat Control SMART BATT HTL Battery operated Remote Control with Thermostat Control GP30 C...

Page 26: ...1 1 1 3 4 0 8 6 2 3 0 8 6 2 2 0 8 6 2 6 3 y l b m e s s A n e e r c S 3 3 y l b m e s s A n e e r c S 0 3 y l b m e s s A n e e r c S 1 1 1 4 2 1 7 2 2 1 1 7 2 2 0 1 7 2 2 6 3 e m a r F w s s a l G c...

Page 27: ...s 14 Minimum Installation MI Sections 13 Slip Sections Assembly 14 Through the Wall 9 Vermiculite 18 Vertical Installation 3 Vertical Termination Chimney Height 12 Clearances 11 Multiple Terminations...

Page 28: ...afting caused by tight sealing construction of the structure air handling devices such as exhaust fans or forced air furnaces or other causes 5 use of fuels other than those specified in the Operating...

Reviews: